Figure 3. Sample Humidification Applications

Configuration Variables nviInputType_x = 1 nviNetSensor_x = 0

Control Variables

nviSet1_x = Room Setpoint (0-100%) nviSet2_x = Hi-Limit Setpoint (0-100%) nviRHDem1_x = Room %RH (0-100%)nviRHDem2_x = Hi-Limit %RH (0-100%)

nviDisable_x = 1 Unit Disabled = 0 Unit Enabled

Readable Variables nvoStatus_x = 1 Humidifying

=0 Standby

nvoService_x = 1 Service Required

=0 No Service Required nvoFault_x = 1 Fault

=0 No Fault

nvoSysDemand_x = System Demand(0-100%)

nvoDisable_x = 1 Unit Disabled = 0 Unit Enabled

NHTC

Figure 3. Sample Humidification Applications

Room-Sensed %RH Feedback with Duct Hi-Limit Sensing (0-10V Signal Directly to Humidifier)

10-10

Page 17 2008-02-18