Software requirements for Modbus RTU
Modbus addresses:
4XXXX – R/W 3XXXX - R
Command |
| Description |
|
| MODBUS | Details | |
|
|
|
|
|
| address |
|
|
|
|
|
|
|
|
|
Output Control |
| OFF |
| ON |
| 40262 |
|
|
| Disables the |
| Enables the |
|
|
|
|
| humidifier and |
| humidifier |
|
|
|
|
| places the |
| (humidifier will |
|
|
|
|
| humidifier in |
| operate based |
|
|
|
|
| standby mode |
| on the SET |
|
| 255: inhibit actions of |
|
|
|
| OUTPUT |
|
| |
|
|
|
|
|
| humidifier | |
|
|
|
| command |
|
| |
|
|
|
|
|
| 0: allow normal operation | |
|
|
|
| input) |
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
| After a microprocessor reset, the |
|
|
| ||
|
| default setting for Output Control |
|
|
| ||
|
| shall be OFF. |
|
|
|
| |
|
|
|
|
|
| ||
Set Output |
| Sets the desired steam output from |
| 40264 |
| ||
|
|
|
|
|
| Remotely set humidity | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| reading over network. |
|
| This value shall be zero after a |
|
| Value of 0 to 100 (per | ||
|
|
|
| cent). If no network signal | |||
|
| microprocessor reset |
|
| |||
|
|
|
| for N minutes, reverts to 0. | |||
|
|
|
|
|
|
| |
|
|
|
|
|
| ||
Force Drain |
| When written to (FF), will interrupt |
| 40276 |
| ||
|
| the humidification process and |
|
|
| ||
|
| activate the humidifier drain valve. |
|
|
| ||
|
| After 20 minutes the controller will |
|
| 255 will start the process, | ||
|
| reset this value (00). |
|
| 0 will be accepted, to clear | ||
|
| After a microprocessor reset, the |
|
| if the request has not been | ||
|
|
|
| cleared itself | |||
|
| default setting shall be (00) |
|
| |||
|
|
|
|
| |||
|
|
|
|
|
| ||
Set MODBUS |
| Change the humidifier controller’s |
| 40550 |
| ||
address * |
| MODBUS address. |
|
|
| The value changes will | |
|
|
|
|
|
|
| |
|
| Range is |
|
|
| only take effect following a | |
|
| This setting shall be |
|
| hardware reset of the | ||
|
|
|
| control board. | |||
|
| with a default setting of 1. |
|
| |||
|
|
|
|
| |||
|
|
|
|
|
| ||
Set MODBUS |
| Changes the humidifier’s baud rate. |
| 40552 |
| ||
Baud rate * |
| Range is 4800, 9600, and 19200 |
|
| The value changes will | ||
|
|
|
| ||||
|
| B/sec. |
|
|
| only take effect following a | |
|
| This setting shall be |
|
| hardware reset of the | ||
|
|
|
| control board | |||
|
| with a default value of 9600 B/sec. |
|
| |||
|
|
|
|
| |||
|
|
|
|
|
|
|
|
- 8 -