Maximum | The rated maximum steam production | 30802 |
|
|
|
|
|
production | for the humidifier |
| Value written into Unit type | ||||
|
|
| (40600) is also stored here | ||||
|
|
|
|
|
|
|
|
Alarms | The humidifier shall describe any faults | 30364 |
|
|
|
|
|
| Too long to fill |
| Bit Allocation |
|
| ||
| Excess Current |
| Note More than one bit can be | ||||
| End of cylinder life |
| active at any time. |
|
| ||
| No current |
| Too long to fill = 1 |
|
| ||
|
|
| Excess current = 2 |
|
| ||
|
|
| End of cylinder life = 4 |
|
| ||
|
|
| No Current = 8 |
|
| ||
|
|
|
|
|
|
|
|
Units | Required by the control board for | 40031 |
|
|
|
|
|
| capacity calculations |
| 0: | ||||
Unit type | Required by the control board for | 406000 | Depending on the setting in | ||||
| current and capacity calculations |
| UNITS (Modbus: 40031) |
|
| ||
|
|
| Hex value representing |
|
| ||
|
|
| maximum unit capacity (100% fill | ||||
|
|
| off amps) |
|
| ||
Unit voltage | Required by the control board for | 40610 | Format is Hexadecimal | ||||
| current and capacity calculations |
| numeration table (see below) | ||||
|
|
|
|
|
|
|
|
|
|
|
| Hex |
| Unit |
|
|
|
|
| Value |
| Type |
|
|
|
|
| 0 |
| 110- |
|
|
|
|
|
|
| 120 |
|
|
|
|
| 1 |
| 208 |
|
|
|
|
| 2 |
| 220- |
|
|
|
|
|
|
| 240 |
|
|
|
|
| 3 |
| 230 |
|
|
|
|
| 4 |
| 277 |
|
|
|
|
| 5 |
| 347 |
|
|
|
|
| 6 |
| 380 |
|
|
|
|
| 7 |
| 400 |
|
|
|
|
| 8 |
| 415 |
|
|
|
|
| 9 |
| 440- |
|
|
|
|
|
|
| 480 |
|
|
|
|
| A |
| 550- |
|
|
|
|
|
|
| 600 |
|
Unit phase | Required by the control board for | 40620 | Bit Allocation |
|
| ||
| current and capacity calculations. |
| Single phase = 1 |
|
| ||
|
|
| Three phase = 2 |
|
| ||
|
|
| Three phase (6 electrode) = 4 | ||||
|
|
|
|
|
|
|
|
- 10 -