Nortec Industries None manual Maximum

Models: None

1 20
Download 20 pages 31.93 Kb
Page 12
Image 12

Maximum

The rated maximum steam production

30802

 

 

 

 

 

production

for the humidifier

 

Value written into Unit type

 

 

 

(40600) is also stored here

 

 

 

 

 

 

 

 

Alarms

The humidifier shall describe any faults

30364

 

 

 

 

 

 

Too long to fill

 

Bit Allocation

 

 

 

Excess Current

 

Note More than one bit can be

 

End of cylinder life

 

active at any time.

 

 

 

No current

 

Too long to fill = 1

 

 

 

 

 

Excess current = 2

 

 

 

 

 

End of cylinder life = 4

 

 

 

 

 

No Current = 8

 

 

 

 

 

 

 

 

 

 

Units

Required by the control board for

40031

 

 

 

 

 

 

capacity calculations

 

0: 0-1. 0=LBS, 1=KG

Unit type

Required by the control board for

406000

Depending on the setting in

 

current and capacity calculations

 

UNITS (Modbus: 40031)

 

 

 

 

 

Hex value representing

 

 

 

 

 

maximum unit capacity (100% fill

 

 

 

off amps)

 

 

Unit voltage

Required by the control board for

40610

Format is Hexadecimal

 

current and capacity calculations

 

numeration table (see below)

 

 

 

 

 

 

 

 

 

 

 

 

Hex

 

Unit

 

 

 

 

 

Value

 

Type

 

 

 

 

 

0

 

110-

 

 

 

 

 

 

 

120

 

 

 

 

 

1

 

208

 

 

 

 

 

2

 

220-

 

 

 

 

 

 

 

240

 

 

 

 

 

3

 

230

 

 

 

 

 

4

 

277

 

 

 

 

 

5

 

347

 

 

 

 

 

6

 

380

 

 

 

 

 

7

 

400

 

 

 

 

 

8

 

415

 

 

 

 

 

9

 

440-

 

 

 

 

 

 

 

480

 

 

 

 

 

A

 

550-

 

 

 

 

 

 

 

600

 

Unit phase

Required by the control board for

40620

Bit Allocation

 

 

 

current and capacity calculations.

 

Single phase = 1

 

 

 

 

 

Three phase = 2

 

 

 

 

 

Three phase (6 electrode) = 4

 

 

 

 

 

 

 

 

- 10 -

Page 12
Image 12
Nortec Industries None manual Maximum