Water remains at high level and won’t concentrate:
This is normal on cold
If unit has been operating extensively, observe for normal
Unit drains continually:
May be caused by foaming and/or back pressure, or leaking drain valve.
Cylinder is almost empty, check for magnetic pull on drain solenoid indicating miswiring. If no pull, drain actuator is blocked open; remove, disassemble and clean.
If drain is occurring through activated drain valve, valve is miswired or electronics are faulty - consult factory.
If drain is occurring through the overflow on the fill cup, this is due to abnormal restriction on the steam line and back pressure forces water out of the cylinder; therefore, water cannot concentrate and level must stay high; review installation of steam line to ensure no blockages or excessive static pressure in air system.