DIAGNOSTIC PROCEDURES - TROUBLESHOOTING GUIDE
Unit Status Lamp |
|
|
|
| |
|
| Symptom |
| Corrective actions |
|
Yellow | Green |
|
| ||
|
|
|
| ||
On | On | Maximum water level | This usually happens on initial | ||
|
| inside cylinder. | (normal). |
|
|
|
|
| Water is concentrated with minerals inside the cylinder. |
| |
|
|
| Let unit run, yellow light will disappear when the unit is at full | ||
|
|
| output. This may take a day or two. |
| |
|
|
|
|
| |
Off | Off | No power to the | Check for main power supply fault. |
| |
|
| board. | Turn power switch to ‘Drain’ position. If drain valve is activated | ||
|
|
| |||
|
|
| (sound of solenoid), check connection to the board or board itself. | ||
|
|
| When no sound present, check fuse (replace with 3.0 A if needed), | ||
|
|
| transformer (voltage should be present between fuse holder and | ||
|
|
| ground screw). |
|
|
|
|
|
|
| |
1 flash | Off | Excess current. | Check drain valve operation, drain time, possible drain | restric- | |
sequence |
| Operating amperage | tions. |
|
|
|
| exceeded 130% of | Check if fill valve leaks (not holding supply water). |
| |
|
| rated amps. Water is |
| ||
|
| Back pressure may also cause very conductive water | conditions. | ||
|
| drained from the | |||
|
| cylinder (drain valve | Was the humidifier short cycling? |
| |
|
| on for 10 min.). |
| ||
|
| Check for short cycling. |
| ||
|
|
|
| ||
|
|
| Water conductivity too high. |
| |
|
|
|
| ||
2 flashes in | Off | No current | Check water level in the cylinder - should be more than ¼ full. If | ||
sequence |
| detection for 30 | not check fill rate, 24 VAC voltage on fill valve terminals (unit must | ||
|
| minutes with | be on with call for humidity - green light steady on). Verify fresh | ||
|
| continuous call for | water | supply to the humidifier. Leaking drain valve | |
|
| humidity. | can be at fault | (minerals blocking the plunger). | |
|
|
| If cylinder is more than ¼ full, check primary power, connections to | ||
|
|
| the cylinder, continuity of wires to cylinder. |
| |
|
|
| Are power wires connected to proper terminals on the cylinder? | ||
|
|
| (Color coding) |
|
|
|
|
| Possibly wrong cylinder type. |
| |
|
|
| Low water conductivity. |
| |
|
|
|
| ||
4 flashes in | Off | End of cylinder life - | Check water level in the cylinder, should be about ¾ full. | ||
sequence |
| change cylinder. | Check for foaming if water level lower or cylinder life shorter than | ||
|
|
| expected. |
|
|
|
|
| Change cylinder, clean drain valve. |
| |
|
|
|
|
|
|
|
|
|
|
|
|