Nortec Industries None Diagnostic Procedures - Troubleshooting Guide, Unit Status Lamp, Symptom

Models: None

1 20
Download 20 pages 31.93 Kb
Page 9
Image 9

DIAGNOSTIC PROCEDURES - TROUBLESHOOTING GUIDE

Unit Status Lamp

 

 

 

 

 

 

Symptom

 

Corrective actions

 

Yellow
Green

 

 

 

 

 

 

On

On

Maximum water level

This usually happens on initial start-up after replacing the cylinder

 

 

inside cylinder.

(normal).

 

 

 

 

 

Water is concentrated with minerals inside the cylinder.

 

 

 

 

Let unit run, yellow light will disappear when the unit is at full

 

 

 

output. This may take a day or two.

 

 

 

 

 

 

Off

Off

No power to the

Check for main power supply fault.

 

 

 

board.

Turn power switch to ‘Drain’ position. If drain valve is activated

 

 

 

 

 

 

(sound of solenoid), check connection to the board or board itself.

 

 

 

When no sound present, check fuse (replace with 3.0 A if needed),

 

 

 

transformer (voltage should be present between fuse holder and

 

 

 

ground screw).

 

 

 

 

 

 

 

1 flash

Off

Excess current.

Check drain valve operation, drain time, possible drain

restric-

sequence

 

Operating amperage

tions.

 

 

 

 

exceeded 130% of

Check if fill valve leaks (not holding supply water).

 

 

 

rated amps. Water is

 

 

 

Back pressure may also cause very conductive water

conditions.

 

 

drained from the

 

 

cylinder (drain valve

Was the humidifier short cycling?

 

 

 

on for 10 min.).

 

 

 

Check for short cycling.

 

 

 

 

 

 

 

 

Water conductivity too high.

 

 

 

 

 

2 flashes in

Off

No current

Check water level in the cylinder - should be more than ¼ full. If

sequence

 

detection for 30

not check fill rate, 24 VAC voltage on fill valve terminals (unit must

 

 

minutes with

be on with call for humidity - green light steady on). Verify fresh

 

 

continuous call for

water

supply to the humidifier. Leaking drain valve

 

 

humidity.

can be at fault

(minerals blocking the plunger).

 

 

 

If cylinder is more than ¼ full, check primary power, connections to

 

 

 

the cylinder, continuity of wires to cylinder.

 

 

 

 

Are power wires connected to proper terminals on the cylinder?

 

 

 

(Color coding)

 

 

 

 

 

Possibly wrong cylinder type.

 

 

 

 

Low water conductivity.

 

 

 

 

 

4 flashes in

Off

End of cylinder life -

Check water level in the cylinder, should be about ¾ full.

sequence

 

change cylinder.

Check for foaming if water level lower or cylinder life shorter than

 

 

 

expected.

 

 

 

 

 

Change cylinder, clean drain valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

- 7 -

Page 9
Image 9