Set MODBUS | Change the humidifier controller’s | 40554 |
|
parity * | MODBUS parity. |
| The value changes will only take |
| Range is None, Even, Odd |
| effect following a hardware reset |
| This setting shall be |
| of the control board |
| default setting of Even. |
|
|
Reset Run | Resets the humidifier controller’s run | 40560 |
|
Hour Counter | hour counter to zero hours |
| 255 will start the run hours |
|
|
| counter process. |
|
|
| 0 will be accepted to clear the run |
|
|
| hours counter. |
Current | Buffers the measured current | 40910 | From 0 to maximum (depending |
damping |
|
| on software ability) |
Electrode | The value of the electrode current in | 30850 |
|
current | Amps |
| Hex value representing the |
|
|
| humidifies current in amps |
|
|
| Resolution: 0.10 amps |
|
|
| Example: |
|
|
| 015F (hex) = 35.1 Amps |
Steam output | The current steam output in Kg/Hr. or | 30860 |
|
| LBS/hr |
| Hex value representing the |
|
|
| humidifies steam output in kg/hr |
| See UNITS (Modbus 40031) |
| Resolution: 0.10 kg or LBS |
|
|
| Example: |
|
|
| 013B (hex) = 31.5 kg/hr or |
|
|
| LBS/hr |
Run hour | The number of hours the humidifier | 30414 |
|
counter | has been in operation since the last |
| Hex value representing the |
| time the run hour counter was reset |
| number of humidifier operational |
|
|
| hours since the last reset. |
|
|
| Resolution: 5 minutes |
|
|
| Maximum count: 5460 Hours. |
|
|
| Example: |
|
|
| 07D0 = 2000 hours |
Firmware | The firmware version of the humidifier | 30361 |
|
version | controller |
| Packed BCD version 3.52 would |
|
|
| be 0x0352 |
Humidifier state | Describes the current state of the | 30800 |
|
| humidifier and it’s I/O’s |
| Bit Allocation |
| Contactor ON/OFF |
| Note More than one bit can be |
| Fill Valve ON/OFF |
| active at any time. |
| Drain Valve ON/OFF |
| Contactor on = 1 |
|
|
| Fill valve on = 2 |
|
|
| Drain valve on = 4 |
- 9 -