WATER SUPPLY AND PLUMBING

WATER SUPPLY AND PLUMBING

1.The fill valve is sized for an extended water pressure range of 30 to 80 psi.

2.For cases below 15 psi add a pressure boost pump, notify the factory and a fill valve with an oversized orifice will be supplied.

3.For cases above 80 psi, install a pressure reducing valve in the water feed line to the unit.

4.With extremely dirty or muddy water sources, e.g., some well sources, ensure proper filtration by adding an external filter to the water line entering the unit. (Consult factory for accessories such as filters.)

5.DO NOT use completely demineralized water with this unit as it is the minerals that allow the electrode principle to work.

6.DO NOT use a hot water source as it will cause deposits that will eventually block the fill valve orifice.

Figure #2

Bottom View of MES-U/MES-P Unit

3/8" Cold Water

Olive Connection

7/8" Drain

Connection

Use 7/8" I.D. Hose From Factory

.

WATER CONNECTION

1.A copper compression olive type coupling for 1/4" O.D. soft copper tubing is provided with unit and requires no soldering for the water connection to the unit. See Figure #2.

2.An isolating valve should ALWAYS be placed in the feed water line allowing service of the fill valve.

3.Each unit is fitted with a fill solenoid valve located on the base drain pan. Flow orifices

are designed for water pressure from 30 to 80 psi and are protected by the built-in strainer.

4.For inlet water pressure outside this range, the factory should be contacted. (See Water Supply and Plumbing section of this manual.)

START-UP AND OPERATION

￿Ambient temperature location for humidifier: 41ºF - 104ºF (5ºC - 40ºC).

￿Relative humidity location for humidifiers: 5% rh - 80% rh.

Check to see that the unit is securely mounted on a level surface with the proper drain and water supply. Check for correct voltage with appropriately sized service. Check that the steam distributor, steam supply hose, and condensate line are correctly installed and routed back to the unit. Ensure that the external control humidistat is located in an area to properly sense the relative humidity to be maintained by the humidifier, and that the interconnecting low voltage wires between the humidistat and the unit’s control terminal strip are in accordance with the wiring diagram.

Check all electrical connections for wires which may have become loose in shipping. Components damaged due to loose connections are NOT under warranty.

Check electrode plugs to ensure they are pressed firmly onto the electrode pins. Important: Loose connections will cause overheating of the cylinder plugs, possibly melting the plugs and/or cylinder.

Open the isolating valve in the feed water line to the unit.

Make sure the humidistat is set high enough to call for humidification.

Turn on the main disconnect in the primary service feeding the unit and check that unit has power at the primary terminal block.

PUSH THE AUTO ON/OFF/DRAIN SWITCH TO “ON”.

Water will start to enter the cylinder through its bottom port and rise in the cylinder to a point determined by the solid-state control circuitry.

It is not unusual upon initial start-up for the water to fill the cylinder and cycle on the red high water sensor light.

- 2 -

Page 4
Image 4
Nortec Industries None manual Water Supply And Plumbing, Start-Upand Operation, Figure #2 Bottom View of MES-U/MES-PUnit