Overview

 

 

 

Section 6-1

 

 

 

 

 

 

Item

 

Specification

 

 

 

Response monitoring time

Default setting:

2 s

 

 

 

User setting:

0.1 to 6553.5 s

 

 

 

 

 

Retries

 

 

0 to 15

 

 

 

 

 

FINS mes-

Received from CS/CJ-

Supported (Data send/receive or FINS commands).

sage com-

series CPU Unit with CS/

 

 

munications

CJ-series DeviceNet Unit

 

 

commands

 

 

 

 

Received from CVM1/CV-

Not supported.

 

 

 

 

series CPU Units with

 

 

 

CVM1/CV-series DeviceNet

 

 

 

Master Unit

 

 

 

 

 

 

 

Received from CS/CJ-

 

 

 

series and C200HX/HG/HE

 

 

 

CPU Units with C200H-

 

 

 

series DeviceNet Master

 

 

 

Unit

 

 

 

 

 

 

 

Received from C200HX/HG/

 

 

 

HE Units with C200H-series

 

 

 

DeviceNet Master Unit

 

 

 

 

 

 

Internetwork connections

Same net-

Supports internetwork communications between DeviceNet networks with

 

 

work type

CS/CJ-series DeviceNet Units mounted (up to 3 levels).

 

 

 

 

 

 

Different net-

Supports internetwork communications between DeviceNet networks with

 

 

work type

CS/CJ-series DeviceNet Units mounted and other networks (Controller

 

 

 

Link, SYSMAC LINK, and Ethernet; up to 3 levels).

 

 

 

Message monitor timer function (explicit

The response monitoring time for DeviceNet Units during explicit message

message communications)

communications (the interval the explicit connection is open) can be set

 

 

 

from the Configurator for each device. (The settings for all devices can be

 

 

 

stored in the DeviceNet Unit. This is called the Message Monitoring Timer

 

 

 

List.)

 

 

 

 

 

 

6-1-5 Message Communications Error Indications

There are two ways to obtain information on communications errors that occur in message communications: 1) Using the error history in the DeviceNet Unit and 2) Using DeviceNet Unit displays, indicators, and Master Status Areas.

1,2,3... 1. Each time a communications error occurs, an error code is placed in an er- ror record in the error history kept in the RAM of the DeviceNet Unit. Up to 64 records can be stored in the error history. The time and data the record occurred is also recorded.

The error history can be read or cleared from the CPU Unit by sending an FINS command to the DeviceNet Unit (Error History Read/Clear). The con- tents of the error history can also be monitored from the Configurator.

Code

Code

Code

64 records

FINS command Read-out

Monitor

CPU Unit

Configurator

2.The MS and NS indicators and the 7-segment display on the front panel of the DeviceNet Unit can be used together with the Master Status Area 1 in the CPU Unit to obtain information on a communications error that has oc- curred. This information can be used as the basis for troubleshooting.

139

Page 150
Image 150
Omron CS1W-DRM21, CJ1W-DRM21 operation manual Message Communications Error Indications, List