Troubleshooting with the DeviceNet Unit Indicators

 

Section 9-1

 

Correction

 

 

 

 

Clear the scan list and register the scan list again or use the Configurator to

 

reset the master scan list.

 

 

Memory Access Error

 

 

 

 

 

7-segment

MS indicator

NS indicator

Error log (Hex)

 

 

 

 

 

 

E9

Red (flashing)

---

0602

 

 

 

 

 

 

Likely Cause

 

 

 

 

An error occurred in the Unit’s non-volatile memory itself. This error will occur

 

in the following cases.

 

 

1,2,3...

1. An error occurs reading the identity information during initialization

2.All 64 error log records cannot be used during initialization or registering an error log record

3.An error occurs while reading or writing the error log

4.An error occurs while reading or writing the master function enabling data or the master scan list

5.An error occurs while reading or writing the slave function enabling data or the slave scan list

6.An error occurs while reading or writing the message monitoring timer

7.An error occurs while reading or writing the communications cycle time set value

8.An error occurs while reading the identity information during Identity object server processing

Note This error does occur for checksum errors while reading data.

DeviceNet Unit Response

Registers an error record with error code 0602 in the RAM error log area.

For error 1:

Normal operation continues

For error 2 or 3:

Remaining writes to EEPROM are all ignored. Other than that, normal opera- tion continues. (Error records continue to be written to RAM.)

For error 4:

The master remote I/O communications are stopped. Other operations con- tinue.

For error 5:

The slave scanning is stopped and other operations continue.

For error 6:

The default values are used for the message monitoring timer and operation continues.

For error 7:

The communications cycle time is set automatically and operation continues.

For error 8:

Operation continues.

Flags Allocated for C200H DeviceNet Master Unit (CIO n+24)

Bit 14 (Error Flag) and bit 00 (the Incorrect Switch Settings/EEPROM Error

Flag) will be ON.