Omron CJ1W-DRM21, CS1W-DRM21 operation manual Comparison with Previous Models

Models: CJ1W-DRM21 CS1W-DRM21

1 274
Download 274 pages 23.02 Kb
Page 45
Image 45

 

Comparison with Previous Models

Section 1-4

 

 

 

 

 

Item

C200HW-DRM21-V1

CS1W-DRM21/CJ1W-DRM21

 

 

 

 

 

 

Remote I/O

Fixed alloca-

C200H DeviceNet words in CIO Area

CS/CJ-series DeviceNet words in CIO Area

 

communica-

tions

1,600 points (50 input words, 50 output

2,048 points (64 input words, 64 output

 

tions Master

 

words)

words)

 

 

 

 

 

 

 

 

Output area: CIO 0050 to CIO 0099

Select one of the following using the soft-

 

 

 

Input area: CIO 0350 to CIO 0399

ware switch.

 

 

 

 

Output area: (1) CIO 3200 to CIO 3263

 

 

 

 

(2) CIO 3400 to CIO 3463

 

 

 

 

(3) CIO 3600 to CIO 3663

 

 

 

 

Input area: (1) CIO 3300 to CIO 3363

 

 

 

 

(2) CIO 3500 to CIO 3563

 

 

 

 

(3) CIO 3700 to CIO 3763

 

 

 

 

 

 

 

 

Node addresses: 0 to 49, node address

Node addresses: 0 to 63, node address

 

 

 

order, 1 word/node address

order, 1 word/node address

 

 

 

 

 

Slaves with 8 points: Require 1 word even though they are allocated the rightmost byte (requires 1 node address)

Slaves with 16 points: Require 1 word (require 1 node address)

Slaves with over 16 points: Require multiple words (require multiple node addresses)

User-set allo- Set by the Configurator.

Set from allocated DM Area words (Master

cations

User Allocation Setup Table) or the Configu-

 

 

rator.

 

 

 

 

When using the message communications

When set from allocated DM Area words:

 

function:

16,000 pts max. (8,000 input words, 8,000

 

1,600 pts max. (800 input words, 800 output

output words)

 

words)

When set from the Configurator:

 

 

 

When not using the message communica-

32,000 pts max. (16,000 input words, 16,000

 

tions function:

output words)

 

4,800 pts max. (2,400 input words, 2,400

 

 

output words)

 

 

 

 

 

The following areas can be set:

The following areas can be set:

 

CIO: 0000 to 0235, 0300 to 0511

CIO: 0000 to 6143

 

CIO: 1000 to 1063

WR: W000 to W511

 

HR: HR000 to HR099

HR: HR000 to HR511 words

 

DM: D00000 to D05999

DM: D00000 to D32767

 

 

EM: E00000 to E32767 (Banks 0 to C sup-

 

 

ported)

 

 

 

 

OUT 1, OUT 2, IN 1, and IN 2, for a total of 4

Any position in the allocation areas given

 

blocks can be set at any size (total for 1 to 4

above.

 

blocks) at any position in the allocation

Using allocated DM Area words: Total of two

 

areas given above.

 

block, OUT 1 and IN 1.

 

 

 

Any node addresses can be set within a

Using the Configurator: A total of 4 blocks,

 

block.

 

OUT 1, OUT 2, IN 1, and IN 2

 

 

 

 

 

 

With a total of 4 blocks and a maximum of

500 words max. per block

 

100 words per block, the maximum number

Using allocated DM Area words:

 

of words is 100 using message communica-

 

1,000 words total for 2 blocks

 

tions and 300 without using the message

Using the Configurator:

 

communications.

 

2,000 words total for 4 blocks

 

 

 

 

 

 

Maximum of 32 input words, 32 output

Using 2 connections:

 

words per slave.

Maximum of 200 input words, 100 output

 

 

words per slave.

 

 

Using 1 connection:

 

 

Maximum of 100 input words, 100 output

 

 

words per slave.

 

 

 

 

There are the following restrictions.

 

The bytes 7 to 15 cannot be used for start bytes for slaves with more than 8 points.

More than one master cannot share a slave.

Slaves with 8 points: Require the leftmost or rightmost byte (does not require 1 word)

Slaves with 16 points: Require 1 word

Slave with over 16 points: Require multiple words (the last byte will be the rightmost byte with an odd number of bytes)

30