Errors that May Occur in Remote I/O Communications

 

Section 4-7

 

 

 

 

 

 

Condition

Error

Details

Results

Indicators

7-

 

 

 

 

 

segment

 

 

 

 

 

display

 

 

 

 

 

 

Fixed or

I/O communications error

A timeout occurred during remote

Reconnect with

MS: Not

d9

user-set

 

I/O communications. (The Slave

the error Slave

related

 

allocations

 

response timed out 6 times in a

and continue

NS:

 

 

 

row or an error occurred 3 times in

remote I/O com-

 

 

 

Flashes

 

 

 

a row.)

munications.

 

 

 

red

 

 

 

 

*1

 

 

 

 

 

 

 

Network power error

The network is not supplying com-

MS: Not

E0

 

 

 

 

munications power.

 

related

 

 

 

 

 

NS: Goes

 

 

Send timeout

A communications request was

 

E2

 

 

not successfully completed due to

 

out

 

 

 

the following reasons:

 

 

 

 

 

• There are no devices on the net-

 

 

 

 

 

work.

 

 

 

 

 

• Baud settings do not match for

 

 

 

 

 

every node.

 

 

 

 

 

• CAN controller error

 

 

 

 

 

 

 

 

 

 

Duplicated node address

The master node address is the

All communica-

MS: Not

F0

 

 

same address as another node.

tions stop (remote

related

 

 

 

 

I/O communica-

NS:

 

 

Bus OFF detected

Bus OFF error was detected.

F1

 

tions stop, slave

 

 

 

Flashes

 

 

 

 

operation stops,

 

 

 

 

red

 

 

 

 

and message

 

 

 

 

 

 

 

 

 

communications

 

 

 

 

 

are disabled).

 

 

 

 

 

 

 

 

 

Master scan list logic error

The master scan list data is incor-

Remote I/O com-

MS:

E8

 

 

rect.

munications stop

Flashes

 

 

 

 

(Slave operation

red

 

 

 

 

stops, but mes-

NS: Not

 

 

 

 

sage communica-

 

 

 

 

related

 

 

 

 

tions are

 

 

 

 

 

 

 

 

 

enabled).

 

 

 

 

 

 

 

 

Note Remote I/O communications will stop (7-segment display: A0) if DIP switch pin 3 on the front panel is turned ON to specify stopping remote I/O communi- cations for I/O communications errors.