Fixed Allocations

Section 4-3

Note More than one Master Unit can be included in a single PC with fixed alloca- tions, as shown below (3 Units max.).

Master Unit

Master Unit

Slave

Slave

4-3-2 Procedure

Step 1: Place the CPU Unit in PROGRAM mode.

Step 2: Turn ON the

If the master communications have been disabled (if Master Function Enable

Master Enable Switch

Flag (word n+11, bit 03) is OFF), turn ON the Master Enable Switch (word n,

 

bit 06) to enable master communications. Once Master communications have

 

been enabled by turning this switch ON, it will not change even if the power is

 

turned OFF and back ON again.

 

Note If the master communications are enabled (if Master Function Enable

 

Flag (word n+11, bit 03) is ON), skip this step and go onto the next

 

step. (If the Master Enable Switch is turned ON when master com-

 

munications are enabled, a Unit error will occur and a C2 error will be

 

displayed on the 7-segment display on the front panel.)

Step 3: Turn ON the Scan If the Unit is in the Scan List Enable mode (if Scan List Disabled Flag (word

List Clear Switchn+11, bit 04) is OFF), turn ON the Scan List Clear Switch (word n, bit 01) to change to the Scan List Disable mode.

 

 

 

Note If the Unit is already in the Scan List Disable mode (if the Scan List

 

 

 

 

Disabled Flag (word n+11, bit 04) is ON), skip this step and go onto

 

 

 

 

the next step. (If the Scan List Clear Switch is turned ON when the

 

 

 

 

Unit is in the Scan List Disable mode, a Unit error will occur and a C2

 

 

 

 

error will be displayed on the 7-segment display on the front panel.)

Step 4: Select Fixed

Turn ON the Master Fixed Allocation Setting 1 to 3 Switch (word n, bits 08 to

Allocations Area 1 to 3

10) in the Software Switches in the words allocated in the CIO Area to select

 

 

the fixed allocations area from1 to 3. One word will be allocated per node

 

 

address in order of node addresses for the output (OUT) block and one word

 

 

for the input (IN) block in the CS/CJ-series DeviceNet CIO Area.

 

 

 

 

 

 

First word n = CIO 1500 + (25 x unit number)

 

 

 

 

 

 

 

 

Software Switch

 

Software Switch name

Fixed allocations

Allocated

Allocated

 

address

 

 

 

area number

OUT area

IN area

 

Word n, bit 08

 

 

Master Fixed Allocation

Fixed allocations area

CIO 3200 to

CIO 3300 to

 

 

 

 

Setting 1 Switch

1

CIO 3263

CIO 3363

 

 

 

 

 

 

 

 

 

Word n, bit 09

 

 

Master Fixed Allocation

Fixed allocations area

CIO 3400 to

CIO 3500 to

 

 

 

 

Setting 2 Switch

2

CIO 3463

CIO 3563

 

 

 

 

 

 

 

 

 

Word n, bit 10

 

 

Master Fixed Allocation

Fixed allocations area

CIO 3600 to

CIO 3700 to

 

 

 

 

Setting 3 Switch

3

CIO 3663

CIO 3763

 

 

 

 

 

 

 

 

Step 5: Turn ON the Scan Remote I/O communications will start with the scan list disabled after a fixed

List Enable Switchallocations area has been selected. Check to see if communication is pro- ceeding normally with each slave, and then turn ON the Scan List Enable Switch (word n, bit 00) to communicate with the scan list enabled.

102

Page 115
Image 115
Omron CJ1W-DRM21, CS1W-DRM21 Procedure, Place the CPU Unit in Program mode Turn on, Master Enable Switch, Select Fixed