Conformance to EC Directives

6

6

Conformance to EC Directives

 

 

6-1

Applicable Directives

 

 

 

 

 

• EMC Directives

 

 

 

6-2

Concepts

 

 

 

 

 

 

EMC Directives

 

 

 

 

 

OMRON devices that comply with EC Directives also conform to the related

 

 

EMC standards so that they can be more easily built into other devices or

 

 

machines. The actual products have been checked for conformity to EMC

 

 

standards. (See the following note.) Whether the products conform to the

 

 

standards in the system used by the customer, however, must be checked by

 

 

the customer.

 

 

 

 

 

EMC-related performance of the OMRON devices that comply with EC Direc-

 

 

tives will vary depending on the configuration, wiring, and other conditions of

 

 

the equipment or control panel in which the OMRON devices are installed.

 

 

The customer must, therefore, perform final checks to confirm that devices

 

 

and the overall machine conform to EMC standards.

 

Note

Applicable EMS (Electromagnetic Susceptibility) and EMI (Electromagnetic

 

 

Interference standards in the EMC (Electromagnetic Compatibility) standards

 

 

are as follows:

 

 

 

 

 

 

 

 

 

 

 

Unit

EMS

EMI

 

 

 

 

 

 

 

 

 

CS1W-DRM21

EN50082-2

EN50081-2

 

 

 

 

 

 

 

 

 

CJ1W-DRM21

EN61000-6-2

 

 

 

 

 

 

 

 

6-3

Conformance to EC Directives

 

 

 

 

DeviceNet products that meet EC directives must be installed as follows:

 

1,2,3...

1. DeviceNet Units are designed for installation inside control panels. All De-

 

 

viceNet Units must be installed within control panels.

 

 

2. Used reinforced insulation or double insulation for the DC power supplies

 

 

used for the communications power supply, internal circuit power supply,

 

 

and the I/O power supplies.

 

 

 

 

3. DeviceNet products that meet EC directives also meet the common emis-

 

 

sion standard (EN50081-2). When DeviceNet products are built into equip-

 

 

ment, however, the measure necessary to ensure that the standard is met

 

 

will vary with the overall configuration of the control panel, the other devic-

 

 

es connected to the control panel, and other conditions. You must there-

 

 

fore confirm that EC directives are met for the overall machine or device,

 

 

particularly for the radiated emission requirement (10 m).

 

 

The following examples show means of reducing noise.

 

1,2,3....

1. Noise from the communications cable can be reduced by installing a ferrite

 

 

core on the communications cable within 10 cm of the DeviceNet Unit.