Omron CJ1W-DRM21 Outline of Functions, Backing Up Unit Setup Files, Restoring Unit Setup Files

Models: CJ1W-DRM21 CS1W-DRM21

1 274
Download 274 pages 23.02 Kb
Page 197
Image 197

Memory Card Backup Functions

Section 7-2

DeviceNet Unit

CPU Unit

Unit Setup File Backup Switch

 

 

 

Unit Setup File Restore Switch

All setup

 

Configurator (computer)

 

Memory Card

data

 

 

 

 

Backup

Save file

Restore

Load file

7-2-1 Outline of Functions

1. Backing Up Unit Setup Files

Saves all internal Unit setup data to the Memory Card mounted to the CPU Unit.

Method: Turn ON the Setup File Backup Switch (word n+1, bit 15) to save the internal Unit setup data to the Memory Card as a Unit Setup File.

DeviceNet Unit

CPU Unit

 

Unit Setup File Backup switch

data

Memory Card

Backup

2. Restoring Unit Setup Files

Restoring Unit Setup Files involves reading the data and setting it to a Unit. The data saved to the Memory Card mounted to the CPU Unit is read to the Unit.

Method: Turn ON the Unit Setup File Restore Switch (word n+1, bit 14) to read the Unit setup data file on the Memory Card and to enable these settings as the Unit settings.