Fixed Allocations

Section 4-3

you disable the scan list with a Master Unit that is set for user-set allocations. Particularly when multiple Master Units are connected to a single network, communications will not be performed suc- cessfully if even one Master Unit on the network is operating with the scan list disabled. Once the list is disabled, the user-set allo- cations data registered in the Master Unit is lost.

Backing Up the Scan List

Fixed Allocations or User- set Allocations in Allocated DM Area Words

User-set Allocations from the Configurator

A scan list must be created to switch the DeviceNet Unit to operation with the scan list disabled or to replace a DeviceNet Unit. It is important to back up the list using one of the following methods:

Save the scan list as a backup file on Memory Card by turning ON the Setup File Backup Switch (word n+1, bit 15) in the words allocated in the CIO Area.

Save the scan list as a backup file on Memory Card or save it either as a net- work component file and master parameter file using the Configurator. In the preceding cases, turn ON the Setup File Restore Switch (word n+1, bit 14) in the words allocated in the CIO Area to input setup data, such as the scan list backed up on Memory Card, into a DeviceNet Unit.

4-3

Fixed Allocations

 

 

4-3-1

Allocated Words

 

 

 

 

Words in the CS/CJ-series DeviceNet CIO Area in the CPU Unit are allocated.

 

 

An area of words can be selected from one of three fixed allocation areas.

 

 

Use a Software Switch to select the allocation area.

 

 

Each area is comprised of an OUT area that is used to write output data to

 

 

slaves and an IN area that is used for input from slaves in remote I/O commu-

 

 

nications.

 

 

 

 

 

 

 

 

Area

OUT area (word)

IN area (word)

Selection method

 

 

 

 

Fixed allocation area 1

CIO 3200 to CIO 3263

CIO 3300 to CIO 3363

Turn ON the Master Fixed Allocation Setting

 

 

 

 

1 Switch (word n, bit 08).

 

 

 

 

Fixed allocation area 2

CIO 3400 to CIO 3463

CIO 3500 to CIO 3563

Turn ON the Master Fixed Allocation Setting

 

 

 

 

2 Switch (word n, bit 09).

 

 

 

 

Fixed allocation area 3

CIO 3600 to CIO 3663

CIO 3700 to CIO 3763

Turn ON the Master Fixed Allocation Setting

 

 

 

 

3 Switch (word n, bit 10).

 

 

 

 

 

A maximum of 3 DeviceNet Units can be included as masters in a single PC because the three allocation areas above are set individually for fixed alloca- tions. The default setting is fixed allocations area 1.

Each OUT/IN area is allocated to a slave according to its node address as shown below. Allocated words are determined by the node address in fixed allocations as shown.

 

 

 

 

Node

 

 

 

 

Area 3

Area 2

Area 1

OUT area

address

IN area

Area 1

Area 2

Area 3

CIO 3600

CIO 3400

CIO 3200

 

 

 

CIO 3300

CIO 3500

CIO 3700

CIO 3601

CIO 3401

CIO 3201

 

 

 

CIO 3301

CIO 3501

CIO 3701

CIO 3602

CIO 3402

CIO 3202

 

 

 

CIO 3302

CIO 3502

CIO 3702

CIO 3661

CIO 3461

CIO 3261

 

 

 

CIO 3361

CIO 3561

CIO 3761

CIO 3662

CIO 3462

CIO 3262

 

 

 

CIO 3362

CIO 3562

CIO 3762

CIO 3663

CIO 3463

CIO 3263

 

 

 

CIO 3363

CIO 3563

CIO 3763

101

Page 114
Image 114
Omron CS1W-DRM21, CJ1W-DRM21 operation manual Fixed Allocations, Allocated Words, Backing Up the Scan List, Nications