Master Remote I/O CommunicationsSection 4-1

4-1-2

Remote I/O Master Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

 

Specifications

 

 

 

 

 

 

 

 

 

 

 

Slave alloca-

Fixed allo-

Select one of the following fixed allocation areas using the Fixed Allocated Area Switches 1,

tion methods

cations

2, and 3 in the software switches in the allocated CIO Area words.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Allocated

 

I/O

Size

 

Fixed Alloca-

Fixed Alloca-

Fixed Alloca-

 

 

 

words (CIO

 

 

 

 

tion Area Set-

tion Area Set-

tion Area Set-

 

 

 

Area)

 

 

 

 

ting 1

ting 2

ting 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

64 words

 

3200 to 3263

3400 to 3463

3600 to 3663

 

 

 

 

 

(OUT) area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input (IN)

64 words

 

3300 to 3363

3500 to 3563

3700 to 3763

 

 

 

 

 

area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select one of the above areas using the software switches. All are fixed at 1

 

 

 

 

 

word per node address. The default setting is Fixed Allocation Area Setting

 

 

 

 

1.

 

 

 

 

 

 

 

 

 

 

 

 

 

User-set

By allocated

 

Set the areas and the first words for the OUT 1 and IN 1 blocks in the scan

 

 

allocations

DM Area

 

list Setup Table in the allocated DM Area words. Set the allocation size for

 

 

 

words

 

each slave using the allocation size Setup Table (any words). Allocations

 

 

 

 

 

must be in the order of node addresses.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Allocated

The input and output areas can be the following sizes starting

 

 

 

 

 

words

from any word in any of the following areas: CIO Area, WR

 

 

 

 

 

 

Area, HR Area, DM, Area, or EM Area.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output (OUT)

 

500 words max. 1 block

 

 

 

 

 

 

 

area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input (IN)

 

500 words max. 1 block

 

 

 

 

 

 

 

area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

By Configu-

 

Set the areas for the OUT 1/2 and IN 1/2 blocks, the first words, and the allo-

 

 

 

rator

 

cation sizes for all slaves using the Configurator. Blocks can be set for nodes

 

 

 

 

 

in any order.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Allocated

The input and output areas can be the following sizes starting

 

 

 

 

 

words

from any word in any of the following areas: CIO Area, WR

 

 

 

 

 

 

Area, HR Area, DM, Area, or EM Area.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output (OUT)

 

500 words max. 2 blocks

 

 

 

 

 

 

 

area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input (IN)

 

500 words max. 2 blocks

 

 

 

 

 

 

 

area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No. of Mas-

 

Fixed allocations

 

3 Units max. (Unique words must be allocated using the Allocated CIO Area

ters that can

 

 

 

Words Software Switches.)

 

 

 

be mounted

 

 

 

 

 

 

 

 

 

 

 

User-set

By allocated

 

16 Units max. (Unique words must be allocated using the user Setup Table in

 

 

 

 

 

allocations

DM Area

 

the allocated DM Area words.)

 

 

 

 

 

 

words

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

By Configu-

 

16 Units max. (Unique words must be allocated using the Configurator.)

 

 

 

rator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. No. of

 

Fixed allocations

 

63 nodes

 

 

 

 

 

slaves con-

 

 

 

 

 

 

 

 

 

 

 

User-set

By allocated

 

 

 

 

 

 

 

nected per

 

 

 

 

 

 

 

 

 

allocations

DM Area

 

 

 

 

 

 

 

DeviceNet Unit

 

 

 

 

 

 

 

 

words

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

By Configu-

 

 

 

 

 

 

 

 

 

 

rator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. No. of I/O

Fixed allocations

 

2,048 pts (64 input words, 64 output words)

 

 

points per

 

 

 

 

 

 

 

 

 

 

 

User-set

By allocated

 

16,000 pts (500 input words x 1 block, 500 output words x 1 block)

DeviceNet Unit

 

allocations

DM Area

 

 

 

 

 

 

 

 

 

 

words

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

By Configu-

 

32,000 pts (500 input words x 2 blocks, 500 output words x 2 blocks)

 

 

 

rator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95

Page 108
Image 108
Omron CS1W-DRM21, CJ1W-DRM21 operation manual Remote I/O Master Specifications, Slave alloca Fixed allo