User-set Allocations

Section 5-3

Setting through the

A maximum of three blocks can be allocated at any locations in I/O memory

Configuration

for the output (OUT) area block 1, input (IN) area block 1, and input (IN) area

 

block 2.

Specified area in I/O memory

 

User-set block order

 

Bit

15

0

First word

 

 

 

specified

 

 

 

 

 

Slave output

 

to

 

(OUT) area 1

 

 

 

 

 

 

 

 

Master

OUT area

Bit

First word specified

to

150

Slave input (IN) area 1

IN area

Bit

First word specified

to

150

Slave input (IN) area 2

IN area

The block allocation order and block allocation areas can be set as required. Refer to the DeviceNet Configurator Operation Manual (W382) for details on the allocation procedure.

5-3-3 Connection Types

The type of connection can be specified if the Configurator is used for set- tings. The number of applicable allocation areas varies with the type of con- nection used.

A maximum of three areas (OUT 1, IN 1, and IN 2) can be used when multiple connections are specified.

Two allocation areas (OUT 1 and IN 1) can be used if the automatic con- nection setting or a single connection is specified.

130

Page 142
Image 142
Omron CS1W-DRM21, CJ1W-DRM21 operation manual Setting through, Configuration, Block