Allocated DM Area Words

Section 3-3

Word Bit 15

Bit 00

m

Communications cycle time setting (ms)

Name

Range

Details

 

 

 

Communications

0000 to 01F4 Hex

Sets the communications cycle time in milli-

Cycle Time Set-

(0 to 500)

seconds. Setting range: 0 to 500 ms

ting

 

If this bit is set to 0, the optimum time calcu-

 

 

 

 

lated by the Unit will be used. If a value

 

 

higher than 500 ms is set, then the Unit will

 

 

operate at 500 ms.

 

 

If the setting cannot be correctly made for

 

 

some reason, the Scan List Register/Clear

 

 

Failed Flag (word n+12, bit 11) in Master Sta-

 

 

tus 1 and the Temporary Setting Switch for

 

 

Communications Cycle Time (word n, bit 12)

 

 

will be turned OFF.

 

 

 

Note If the setting is smaller than the optimum communications cycle time calcu- lated by the Unit and stored internally in the Unit, then the value calculated by the Unit will be used.

3-3-2 Master User Allocations Setup Table

This table is set by the user to specify the I/O words used by the master. Only

OUT block 1 and IN block 1 can be set using this table.

Word Bit 15

Bit 08

Bit 07

Bit 00

m+1

 

Reserved by system

OUT block 1 area

 

 

 

 

 

 

m+2

 

First word in OUT block 1

 

 

 

 

 

 

m+3

 

Reserved by system

IN block 1 area

 

 

 

 

 

 

m+4

 

First word in IN block 1

 

 

 

 

 

 

 

m+5

 

Reserved by system

Allocation size setup table area

 

 

 

 

 

 

m+6

 

First word in the allocation size setup table

 

 

 

 

 

m+7

 

Setting results

 

 

 

 

 

 

Note OUT blocks 1 and 2 and IN blocks 1 and 2 can be set from the Configurator.

I/O allocations can be updated in the master by setting this table and turning ON the Master User-set Allocations Switch (word n, bit 11). The Unit will restart automatically and start operating with the scan list enabled.

82

Page 95
Image 95
Omron CJ1W-DRM21, CS1W-DRM21 operation manual Master User Allocations Setup Table, Name Range Details