Troubleshooting with the DeviceNet Unit Indicators

Section 9-1

9-1 Troubleshooting with the DeviceNet Unit Indicators

9-1-1 Determining Operating Status from the Indicators

The following table shows the status of the MS and NS indicators and the 7- segment display during normal operation.

 

Indicator status

Network/Unit status

Comments

 

 

 

 

 

MS

NS

7-segment

 

 

 

 

 

 

 

OFF

OFF

OFF

Initializing with PC

Initialization processing with the PC is in progress.

 

 

 

 

Restart the DeviceNet Unit if this status continues

 

 

 

 

for an extended period of time. Replace the CPU

 

 

 

 

Unit and/or DeviceNet Unit if the problem is not cor-

 

 

 

 

rected by restarting.

 

 

 

 

 

ON

OFF

Master’s node

Checking for node address

The node address duplication check is performed

(green)

 

address

duplication

after initialization.

 

 

(flashing)

 

 

 

 

 

 

 

ON

Flashing

Master’s node

Waiting for remote I/O com-

The Unit will have this status until remote I/O com-

(green)

(green)

address

munications

munications are performed with the master or slave

 

 

(flashing)

 

function. (When both functions are operating, the

 

 

 

 

Unit will have this status until remote I/O communi-

 

 

 

 

cations are performed with either function.)

 

 

 

 

 

 

 

Master’s node

Waiting for message commu-

The Unit will have this status when both the master

 

 

address

nications connection

and slave functions are disabled and the Unit is

 

 

 

 

waiting for a connection by message communica-

 

 

 

 

tions.

 

 

 

 

 

ON

ON

Master’s node

Remote I/O or message com-

This is the normal display when the master and/or

(green)

(green)

address

munications in progress.

slave is active.

 

 

 

 

 

ON

ON

- - (flashing)

Scan list operation in

The scan list is being saved in flash memory or the

(green)

(green)

 

progress.

scan list is being cleared.

 

 

 

 

 

200

Page 210