Errors that May Occur in Remote I/O CommunicationsSection 4-7

4-7

Errors that May Occur in Remote I/O Communications

 

 

 

The following errors may occur during remote I/O communications.

 

 

 

 

 

 

 

 

Condition

Error

Details

Results

Indicators

7-

 

 

 

 

 

 

 

segment

 

 

 

 

 

 

 

display

Error

 

Structure

Duplicate I/

The same I/O word is allocated to

Reconnect with

MS: Not

d0

occurs in

 

Error Flag

O area

two or more slaves. (This occurs

the error slave

related

 

fixed allo-

 

(word n+12,

 

whenever a slave that is allocated

and continue

NS:

 

cations

 

bit 04) turns

 

multiple words has one of the

remote I/O com-

 

 

 

Flashes

 

with the

 

ON

 

words allocated to the node

munications.

 

 

 

red

 

scan list

 

 

 

address of another Slave.)

 

 

 

 

 

 

 

 

disabled

 

 

 

 

 

 

 

 

 

I/O area

A slave is allocated an area out-

 

 

d1

 

 

 

 

 

 

 

 

range

side the fixed allocations area.

 

 

 

 

 

 

exceeded

(This occurs whenever slaves are

 

 

 

 

 

 

 

allocated multiple words and a

 

 

 

 

 

 

 

slave is allocated a word beyond

 

 

 

 

 

 

 

node address 63 in the fixed allo-

 

 

 

 

 

 

 

cations area.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unsup-

The I/O size of a slave exceeds

 

 

d2

 

 

 

ported

200 bytes (100 words). (This

 

 

 

 

 

 

Slave

occurs if either the IN or the OUT

 

 

 

 

 

 

 

size exceeds 200 bytes.)

 

 

 

 

 

 

 

 

 

 

 

Error

 

Verification

No slaves

A Slave registered in the scan list

 

 

d5

occurs in

 

Error Flag

present

is not present.

 

 

 

either fixed

(word n+12,

 

 

 

 

 

I/O size

The I/O size registered in the scan

 

 

d6

or user-set

bit 00) turns

 

 

mis-

list does not match the I/O size of

 

 

 

allocations

ON

 

 

 

matched

the slave.

 

 

 

with the

 

 

 

 

 

 

 

 

Note I/O size is compared in 8-

 

 

 

scan list

 

 

 

 

 

 

 

 

 

point (1-byte) units. If I/O

 

 

 

enabled

 

 

 

 

 

 

 

 

 

size is registered at 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

points for example, then an

 

 

 

 

 

 

 

error I/O size mismatch will

 

 

 

 

 

 

 

not occur with a Slave with

 

 

 

 

 

 

 

just one input point con-

 

 

 

 

 

 

 

nected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incorrect

The vendor registered in the scan

 

 

d6

 

 

 

vendor

list does not match the slave ven-

 

 

 

 

 

 

 

dor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incorrect

The device type registered in the

 

 

d6

 

 

 

device type

scan list does not match the slave

 

 

 

 

 

 

 

device type.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incorrect

The product code registered in the

 

 

d6

 

 

 

product

scan list does not match the slave

 

 

 

 

 

 

code

product code.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incorrect

The connection bus registered in

 

 

d6

 

 

 

connection

the scan list is set incorrectly.

 

 

 

 

 

 

bus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unsup-

The slave does not support the

 

 

d6

 

 

 

ported con-

connection registered in the scan

 

 

 

 

 

 

nection

list.

 

 

 

 

 

 

 

 

 

 

 

118

Page 131
Image 131
Omron CJ1W-DRM21, CS1W-DRM21 operation manual Errors that May Occur in Remote I/O Communications