Nomenclature and Functions

Section 2-1

Note

1. The node address is set to 63 at the factory.

 

2.

Any node address from 0 through 63 can be set as long as it hasn’t been

 

 

set on another slave node.

 

3.

If the node address is the same as one set on another node, a node ad-

 

 

dress duplication error will occur and it won’t be possible to start up net-

 

 

work communications.

 

4.

Node address 0 cannot be used for FINS message communication. Use a

 

 

node address other than 0 for FINS message communication.

DIP Switch

The DIP switch on the front of the DeviceNet Unit is used to set the baud rate,

 

whether communications will be continued or stopped when a communica-

tions error occurs, and whether to hold or clear the remote outputs when a communications error occurs in the slave function.

CS1W-DRM21

1 2 3 4

ON

Baud rate

Continue/stop communications for communications error (when used as a master) Hold/clear I/O for communications error (when used as a slave)

CJ1W-DRM21

ON

1 2 3 4 ON

Hold/clear I/O for communications error (when used as a slave)

Continue/stop communications for communications error (when used as a master) Baud rate

The settings of the DIP switch pins are shown in the following table. All pins are set to OFF at the factory.

Pin

Function

 

Setting

 

 

 

1

Baud rate

See the next table.

 

 

 

 

2

 

 

 

 

 

 

 

3

Continue/stop remote I/O communica-

OFF:

Continue communications

 

tions for communication errors (when

ON:

Stop communications

 

used as a master)

 

 

 

 

 

 

 

4

Hold/clear remote outputs for commu-

OFF:

Clear remote outputs

 

nications error (when used as a slave)

ON:

Hold remote outputs

 

 

 

 

Baud Rate

Pins 1 and 2 are used to set the baud rate as shown in the following table.

Pin 1

Pin 2

Baud rate

 

 

 

OFF

OFF

125 kbps

 

 

 

ON

OFF

250 kbps

 

 

 

OFF

ON

500 kbps

 

 

 

ON

ON

Not allowed.

 

 

 

Note 1. Always turn OFF the PC before changing the DIP switch settings.

2.Set the same baud rate on all of the nodes (Master and Slaves) in the Net- work. Any slaves with baud rates different from the master’s rate won’t be able to participate in communications and may cause a communications error between nodes that have been set properly.

50

Page 64
Image 64
Omron CS1W-DRM21, CJ1W-DRM21 operation manual DIP Switch, Baud Rate