Omron CJ1W-DRM21, CS1W-DRM21 operation manual Starting and Stopping Remote I/O Communications

Models: CJ1W-DRM21 CS1W-DRM21

1 274
Download 274 pages 23.02 Kb
Page 129
Image 129

Starting and Stopping Remote I/O Communications

Section 4-5

Configurator Setting Methods

Refer to the DeviceNet Configurator Operation Manual (W382) for setting methods.

4-5 Starting and Stopping Remote I/O Communications

4-5-1 Starting Remote I/O Communications

Remote I/O communications start automatically after the power is turned ON or the Unit is restarted.

The I/O Data Communications Flag (word n+12, bit 15) is turned ON when remote I/O communications is started with at least one slave.

4-5-2 Stopping Remote I/O Communications

 

Remote I/O communications stop under the following user-controlled condi-

 

tions. Message communications can still be performed when the remote I/O

 

communications stop.

Stop Communications

Remote I/O communications stop when the Remote I/O Communications

With All Slaves

Stop Switch (word n, bit 04) is turned ON.

Stop Communications

Remote I/O communications stop when the Disconnect/Connect Switch for

With a Specified Slave

the desired slave (words n+6 to n+9) is turned ON. (Units are disconnected

 

from remote I/O communication when the Disconnect/Connect Switch is

 

turned ON.)

Note

The communications cycle time is not shorter even though a slave has been

 

disconnected from remote I/O communications by turning ON the Disconnect/

 

Connect Switch. (Blank time in the communications cycle will only be

 

increased.)

4-5-3 Restarting Remote I/O Communications

Remote I/O communications restart under the following conditions,

Restart Communications Remote I/O communications restart when the Remote I/O Communications

with All SlavesStart Switch (word n, bit 01 or 03) is turned ON. (Only communications with slaves stopped using the Disconnect/Connect Switch will be restarted.)

Restart Communications Remote I/O communications restart when the Disconnect/Connect Switch for

with Specified Slave the desired slave (words n+6 to n+9) is turned ON. Restoring the unit will have been completed when the Disconnect/Connect Switch turns OFF.)

4-6 Example of Ladder Programming for Remote I/O Communications

When writing ladder programming for remote I/O communications, make sure it performs I/O processing with a Slave under the following conditions:

The I/O Data Communications Flag (word n+12, bit 15) is ON.

The Unit Error Flag (word n+10, bit 00) is OFF.

Example: There is no jump and slave I/O is processed when the JMP(004) instruction input condition is ON in the following instructions. There is a jump and slave I/O is not processed when the JMP(004) instruction input condition is OFF.

116

Page 129
Image 129
Omron CJ1W-DRM21, CS1W-DRM21 Starting and Stopping Remote I/O Communications, Starting Remote I/O Communications