Troubleshooting with the DeviceNet Unit Indicators

Section 9-1

Verification Error: Unsupported Connection

Remote I/O Communications Error

DeviceNet Unit Response

Records the error in the error log.

The master will periodically attempt to reconnect with the slave with the verifi- cation error.

Flags Allocated for C200H DeviceNet Master Unit (CIO n+24)

Bit 14 (Error Flag) and bit 07 (Comparison Error Flag) will be ON.

CIO Area Flags Allocated to DeviceNet Unit

Bit 00 of n+12 (Comparison Error Flag) and bits 00 and 01 of n+10 (Unit Error Flag and Master Function Error Flag) will be ON.

Correction

Inspect the slave and then create the scan list again.

7-segment

MS indicator

NS indicator

Error log (Hex)

 

 

 

 

d6

---

Red (flashing)

0344

 

 

 

 

Likely Cause

The device does not support the I/O service specified in the scan list. (Occurs with the scan list enabled.)

DeviceNet Unit Response

Records the error in the error log.

The master will periodically attempt to reconnect with the slave with the verifi- cation error.

Flags Allocated for C200H DeviceNet Master Unit (CIO n+24)

Bit 14 (Error Flag) and bit 07 (Comparison Error Flag) will be ON.

CIO Area Flags Allocated to DeviceNet Unit

Bit 00 of n+12 (Comparison Error Flag) and bits 00 and 01 of n+10 (Unit Error Flag and Master Function Error Flag) will be ON.

Correction

Inspect the slave and then create the scan list again.

7-segment

MS indicator

NS indicator

Error log (Hex)

 

 

 

 

d9

---

Red (flashing)

0345

 

 

 

 

Likely Cause

A timeout occurred during remote I/O communications using the master func- tion. (The response from the slave timed out 6 consecutive times.)

DeviceNet Unit Response

Records the error in the error log.

The master will periodically attempt to reconnect with the slave with the error, but remote I/O communications will stop if the master is set to stop communi- cations.

Flags Allocated for C200H DeviceNet Master Unit (CIO n+24)

Bit 14 (Error Flag) and bit 06 (Communications Error Flag) will be ON.

CIO Area Flags Allocated to DeviceNet Unit

Bit 02 of n+12 (Remote I/O Communications Error Flag) and bits 00 and 01 of n+10 (Unit Error Flag and Master Function Error Flag) will be ON.

Correction

Check the following:

206

Page 216
Image 216
Omron CS1W-DRM21, CJ1W-DRM21 operation manual Check the following