Error Log Functions

Section 9-2

Installation of terminators at both ends of the trunk line

Excessive noise

Unit Errors

Special Unit Error

7-segment

MS indicator

NS indicator

Error log (Hex)

 

 

 

 

OFF

Red (lit)

OFF

0601

 

 

 

 

DeviceNet Unit Response

 

 

Records the error in the error log.

 

 

Stops the Unit.

 

 

 

Correction

 

 

 

Restart the CPU Unit. Replace the DeviceNet Unit if the error recurs.

9-2

Error Log Functions

 

 

Errors detected by the DeviceNet Unit are stored in the error log along with

 

 

the date and time of their occurrence. The error log can be read, cleared, and

 

 

monitored using FINS commands or a Configurator.

9-2-1

Error Log Table

Error Log Table

Each time an error occurs, one error record is recorded in the DeviceNet

 

 

Unit’s RAM error log table. The table can record up to 64 records. If another

 

 

error occurs when the table is full, the oldest record will be erased to make

 

 

room for the new error record.

 

 

The error log table records the following information.

Error code

Detail code

Time of occurrence (The CPU Unit’s time is used for the time stamp.)

Error Log Storage Area When an error is detected, information on the error and the time stamp are stored in the Unit’s internal RAM as an error log record. Serious errors are recorded in EEPROM as well as RAM. The error log records in EEPROM are retained even when the Unit’s power is turned OFF or the Unit is restarted. The error log records in EEPROM are copied to RAM when the DeviceNet Unit is turned ON.

When the error log is read with a FINS command or from the Configurator, only the error log records in RAM are read. When the error log is cleared with a FINS command or from the Configurator, the error log records in RAM and EEPROM are erased.

Note Refer to 9-2-2 Error Codes and Detail Codes for a table listing the error codes.

Reading and Clearing the The error log table can be read or cleared by sending a FINS command to the

Error LogDeviceNet Unit. Use the DeviceNet Unit’s unit address as the FINS com- mand’s destination unit address. (The unit address is the unit number+10 Hex.)

Refer to the SYSMAC CS/CJ Series Communication Commands Reference Manual (W342) for details on using the FINS commands. Refer to the Appen- dix E FINS Commands and Responses for DeviceNet Units for details on FINS commands addressed to the DeviceNet Unit.