User-set Allocations

Section 4-4

4-4 User-set Allocations

With a CS/CJ-series DeviceNet Unit, remote I/O communications slaves can be allocated in any area (CIO, WR, HR, DM, or EM) using one of the following methods.

Setting through the allocated DM Area words (Master User Allocations Table)

Setting through the Configurator

User-set Allocations Methods

Method

Set through the allocated DM Area

Set through the Configurator

 

 

words (Master User Allocations Table)

 

 

 

 

 

Allocation areas

 

CIO: 0000 to 6143

 

 

 

WR: W000 to W511

 

 

 

HR: HR000 to HR511

 

 

 

DM: D00000 to D32767

 

 

 

EM: E00000 to E32767 (Banks 0 to C)

 

 

 

 

No. of allocated blocks

2 blocks: OUT 1 and IN 1

4 blocks: OUT 1, IN 1, OUT 2 and IN 2

 

 

OUT 1 and IN 1 can be created anywhere

OUT 1, IN 1, OUT 2, and IN 2 can be cre-

 

 

in the above areas.

ated anywhere in the above areas.

 

 

 

Block allocation order

Any order

 

 

 

 

Node address order

Allocations must be in order of node

Any order

 

 

addresses (0 to 63 in ascending order)

Note 1. Node addresses do not have

 

 

Note 1. Not all nodes need to be allo-

 

 

to correspond between blocks.

 

 

cated, reducing the number of

2. One node address cannot be

 

 

words required.

 

 

allocated to different blocks.

 

 

 

 

 

2. Node addresses do not have

 

 

 

to correspond between blocks.

 

 

 

 

Start bit for allocations

All allocations start from bit 00 (Cannot

Allocations can start from bit 00 or bit 08.

 

 

start from bit 08. All allocations are in 1

Allocations starting from bit 08 are in

 

 

word units.)

1-byte units only.

 

 

 

 

Allocation size

Per block

500 words max.

 

 

 

 

 

 

Total size

1,000 words max. for a total of 2 blocks

2,000 words max. for a total of 4 blocks

 

 

 

 

Slave allocation

Slaves with

The leftmost byte (bits 07 to 15) cannot be used.

limits

more than 8

 

 

 

points

 

 

 

 

 

 

Slaves with 8

Allocated to the leftmost or rightmost bytes (not allocated a word)

 

points

 

 

 

 

 

 

 

Slaves with 16

Allocated one word

 

 

points

 

 

 

 

 

 

Slaves with

Allocated multiple words (with an odd number of bytes, only the rightmost byte is allo-

 

more than 16

cated in the last word)

 

 

points

 

 

 

 

 

 

Note Functions will vary as shown below depending on whether allocations are set through the allocated DM Area words (Master User Allocations Table) or through the Configurator.

Words are always allocated to slaves in order of ascending node ad- dresses when allocations are set with the allocated DM Area words. The order can be determined by the user when the Configurator is used. (However, even when using the allocated DM Area words, nodes do not have to be allocated words, reducing the number of words re- quired.)

Only two blocks (OUT 1 and IN 1) can be allocated when setting are made with the allocated DM Area words area, but there are four blocks (OUT 1/2 and IN 1/2) available with the Configurator.

107