Omron CS1W-DRM21, CJ1W-DRM21 Allocated DM Area Words, Communications Cycle Time Setup Table

Models: CJ1W-DRM21 CS1W-DRM21

1 274
Download 274 pages 23.02 Kb
Page 94
Image 94

Allocated DM Area Words

Section 3-3

3-3 Allocated DM Area Words

Data is stored at the offset positions shown in the figure below starting from the first word allocated to the Unit in the DM Area.

The first word can be calculated as follows from the unit number setting:

First word m = D30000 + (25 x unit number)

Word

Bit 15

Bit 00

m

Communications Cycle Time Setup Table

 

m+1

 

 

 

 

to

Master User Allocations Setup Table (7 words)

m+7

 

 

m+8

 

 

to

Slave User Allocations Setup Table (7 words)

 

m+14

 

 

m+15

 

 

to

Communications Cycle Time Reference Table (4 words)

m+18

 

 

m+19

 

 

 

 

to

Master User-set Allocations Reference Table (12 words)

m+30

 

 

m+31

 

 

 

 

to

Slave User-set Allocations Reference Table (12 words)

m+42

 

 

m+43

 

 

to

Slave Detailed Status Table (32 words)

 

m+74

 

 

m+75

 

 

 

 

to

Reserved by system

 

m+99

 

 

 

 

 

 

Direction

Outputs

CPU Unit DeviceNet Unit

I/O

CPU Unit DeviceNet Unit

Inputs

CPU Unit DeviceNet Unit

3-3-1 Communications Cycle Time Setup Table

This table sets the communications cycle time for the master.

The standard communications cycle time can be updated with these switches.

Temporary Setting

Word n, bit 12

Returns to the previous set-

Switch for Com-

 

ting when the power is turned

munications Cycle

 

OFF or the Unit is restarted.

Time

 

 

Communications

Word n, bit 13

Also effective the next time

Cycle Time Refer-

 

the Unit is started, because

ence Table Clear

 

the set value is stored in non-

Switch

 

volatile memory.

 

 

81

Page 94
Image 94
Omron CS1W-DRM21, CJ1W-DRM21 operation manual Allocated DM Area Words, Communications Cycle Time Setup Table