Master Remote I/O Communications

Section 4-1

Fixed Allocations

Any one of the three areas below can be specified as the words allocated in the CIO Area for fixed allocations. The output (OUT) block and the input (IN) block are allocated strictly in order of node addresses in one of the areas shown below.

CS/CJ Series

OUT block 1

CIO 3200 CIO 3201

CIO 3262 CIO 3263

Address 0

Address 1

To Slaves

Address 62

Address 63

CIO 3300

INCIO 3301 block 1

Address 0

Address 1

From Slaves

OUT block 2

CIO 0362 CIO 0363

CIO 3400 CIO 3401

Address 62

Address 63

Address 0

Address 1

To Slaves

Select one.

CIO 3462 CIO 3463

CIO 3500

Address 62 Address 63

Address 0

INCIO 3501 block 2

CIO 3562

CIO 3563

CIO 3600

CIO 3601

OUT

block 3CIO 3662 CIO 3663

Address 1

From Slaves

Address 62

Address 63

Address 0

Address 1

To Slaves

Address 62

Address 63

CIO 3700

INCIO 3701 block 3

CIO 3762

CIO 3763

Address 0

Address 1

From Slaves

Address 62

Address 63

Words are allocated to slaves starting from address 0 in the output (OUT) and

IN blocks. Each address is allocated at least one byte (rightmost).

• More than one word is allocated for each slave (according to its node address) with more than16 I/O points.

• The rightmost byte of the word is allocated to each slave that has less

 

than 16 I/O points.

User-set Allocations

 

 

The following methods are used for user-set allocations:

 

• Using a Master User Allocations Table (allocated DM Area words)

 

• Using the Configurator

Using the Master User

In the Master User Allocations Table, set the areas and first words for the out-

Allocations Table

put block (OUT 1) and the input block (IN 1) and set the area and first word for

 

the Allocation Size Setup Table. In the Allocation Size Setup Table, set the

 

allocation sizes for the slave input and output blocks. Each slave can be allo-

 

cated two blocks, OUT 1 and IN 1, according to the settings in these tables.