Allocated CIO Area Words

 

Section 3-2

 

 

 

 

 

 

 

Bit

 

Name

Status

 

Controlled

Unit operation

 

 

 

 

 

by

 

 

 

 

 

 

 

07

Network

ON

 

Unit

Indicates that there is no power from the network power supply.

 

Power Error

 

 

 

Note Remote I/O communications stop if DIP switch pin 3 (remote I/O

 

Flag

 

 

 

 

 

 

 

communications stop/continue setting for a communications error)

 

 

 

 

 

 

 

 

 

 

 

 

on the front panel is ON (stop).

 

 

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates that the error has not occurred or turns OFF when the network

 

 

 

 

 

 

power supply has restarted.

 

 

 

 

 

 

08

Send Time-

ON

 

Unit

Indicates that a send timeout occurred due to one of the following factors:

 

out Flag

 

 

 

• No slaves present.

 

 

 

 

 

 

 

 

 

 

 

 

• Mismatched baud rate settings.

 

 

 

 

 

 

Note Remote I/O communications stop if DIP switch pin 3 (remote I/O

 

 

 

 

 

 

communications stop/continue setting for a communications error)

 

 

 

 

 

 

on the front panel is ON (stop).

 

 

 

 

 

 

 

 

 

 

OFF

 

Unit

Returns to OFF at the start of communications even with just one slave

 

 

 

 

 

 

present.

 

 

 

 

 

 

09

Reserved by

---

 

---

---

to

system

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

12

Routing

ON

 

Unit

Incorrect data in the routing tables set in the CPU Unit. Refer to 1-6-3 Cre-

 

Table Error

 

 

 

ating Routing Tables.

 

Flag

 

 

 

 

 

OFF

 

Unit

Indicates that the error has not occurred if a routing table has been set.

 

 

 

 

 

 

 

 

 

 

13

Invalid Mes-

ON

 

Unit

Indicates that the data in the message monitoring timer list is not correct.

 

sage Timer

 

 

 

 

 

OFF

 

Unit

Indicates that the data in the message monitoring timer list is correct.

 

List Flag

 

 

 

 

 

Turns OFF if the Configurator registers a message monitoring timer list

 

 

 

 

 

 

 

 

 

 

 

 

when the error occurs.

 

 

 

 

 

 

The message monitoring timer list shows the time spent waiting for

 

 

 

 

 

 

responses in message communications. It is set from the Configurator.

 

 

 

 

 

 

14

Reserved by

---

 

---

---

to

system

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

3-2-6

Unit Status 2 (Word n+11)

Word n+11 [n = CIO 1,500 + (25 x unit number)]

 

 

 

 

 

 

Bit

 

Name

Status

 

Controlled

Unit operation

 

 

 

 

 

by

 

 

 

 

 

 

 

00

Online Flag

ON

 

Unit

Indicates that the Unit is online. The Unit normally goes online automati-

 

 

 

 

 

 

cally.

 

 

 

 

 

 

Note When executing message communications instructions (SEND/

 

 

 

 

 

 

RECV/CMND) from the ladder program, use an AND of input con-

 

 

 

 

 

 

ditions for the Network Communications Enabled Flag in the CPU

 

 

 

 

 

 

Unit (A20200 to A20207) and this bit.

 

 

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates that the Unit is offline. A Unit will go offline under the following

 

 

 

 

 

 

conditions:

 

 

 

 

 

 

• Operation is stopped by the hardware/software check at startup.

 

 

 

 

 

 

• An error occurred in the duplicate node address check (word n+10, bit

 

 

 

 

 

 

06).

 

 

 

 

 

 

• A Bus OFF error has occurred (word n+10, bit 05).

 

 

 

 

 

 

 

72

Page 85
Image 85
Omron CJ1W-DRM21, CS1W-DRM21 operation manual Unit Status 2 Word n+11, Word n+11 n = CIO 1,500 + 25 x unit number