Allocated CIO Area Words

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Section 3-2

 

Bit15

Bit14

Bit13

Bit12

Bit11

Bit10

Bit09

Bit08 Bit07

Bit06

Bit05

Bit04

Bit03

Bit02

Bit01

Bit00

n+6

15

14

13

12

11

 

10

09

 

08

07

06

05

04

03

 

02

01

 

00

 

n+7

31

30

29

28

27

 

26

25

 

24

23

22

21

20

19

 

18

17

 

16

 

n+8

47

46

45

44

43

 

42

41

 

40

39

38

37

36

35

 

34

33

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n+9

63

62

61

60

59

 

58

57

 

56

55

54

53

52

51

 

50

49

 

48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote I/O communications will restart if a user turns OFF a bit that is ON.

More than one of these switches may be turned ON at the same time. If the switch for a slave that is not using remote I/O communications is turned ON, it will be ignored.

A Unit that has been disconnected can still perform message communica- tions.

Turning ON this bit does not effect the communications cycle time (except that it increases blank time in the communications cycle).

Note All Disconnect/Connect Switches are cleared and return to OFF when the power is turned OFF. If required, write the ladder program to turn them back ON when the power is turned ON.

Bit

Name

Status

Controlled

Unit operation

 

 

 

by

 

 

 

 

 

 

Disconnect/

ON

User

Stops remote I/O communications for the corresponding Slave.

 

Connect

 

 

 

 

OFF

User

Starts remote I/O communications for the corresponding Slave.

 

Switch

 

 

 

 

70

Page 83
Image 83
Omron CJ1W-DRM21, CS1W-DRM21 operation manual Bit Name Status Controlled Unit operation