Maintenance and Replacement

Section 9-4

9-4 Maintenance and Replacement

This section describes the routine cleaning and inspection recommended as regular maintenance as well as the Unit replacement procedure required if a DeviceNet Unit fails.

9-4-1 Cleaning

Clean the DeviceNet Units regularly as described below in order to keep the network in its optimal operating condition.

Wipe the Unit daily with a dry, soft cloth.

When a spot can’t be removed with a dry cloth, dampen the cloth with a neutral cleanser (2% solution), wring out the cloth, and wipe the Unit.

A smudge may remain on the Unit from gum, vinyl, or tape that was left on for a long time. Remove the smudge when cleaning.

Never use volatile solvents such as paint thinner, benzene, or chemical wipes.

These substances could damage the surface of the Unit.

9-4-2

Inspection

 

 

 

 

 

 

Be sure to inspect the system periodically to keep it in its optimal operating

 

 

condition. In general, inspect the system once every 6 to 12 months, but

 

 

inspect more frequently if the system is used with high temperature or humid-

 

 

ity or under dirty/dusty conditions.

 

 

Inspection Equipment

Prepare the following equipment before inspecting the system.

 

 

 

Required Equipment

 

 

 

 

Have a standard and Phillips-head screwdriver, multimeter, alcohol, and a

 

 

clean cloth.

 

 

 

 

 

Equipment Required Occasionally

 

 

 

 

Depending on the system conditions, a synchroscope, oscilloscope, ther-

 

 

mometer, or hygrometer (to measure humidity) might be needed.

Inspection Procedure

Check the items in the following table and correct any items that are below

 

!Caution

standard.

 

 

 

 

 

 

 

 

 

 

Item

Standard

Equipment

 

 

Environmental

Ambient and cabinet temperature

0°C to 55°C

Thermometer

 

 

conditions

 

 

 

 

 

Ambient and cabinet humidity

10% to 90%

Hygrometer

 

 

 

 

 

 

(with no condensation or icing)

 

 

 

 

 

 

 

 

 

 

 

Dust/dirt accumulation

None

---

 

 

 

 

 

 

 

 

Installation

Are the Units installed securely?

No looseness

---

 

 

 

 

 

 

 

 

 

Are the communications connec-

No looseness

---

 

 

 

tors fully inserted?

 

 

 

 

 

 

 

 

 

 

 

Are the external wiring screws

No looseness

---

 

 

 

tight?

 

 

 

 

 

 

 

 

 

 

 

Are the connecting cables

No damage

---

 

 

 

undamaged?

 

 

 

 

 

 

 

 

225