Allocated CIO Area WordsSection 3-2

3-2-7

Master Status 1 (Word n+12)

Word n+12 [n = CIO 1,500 + (25 x unit number)]

 

 

 

 

 

Bit

Name

Status

Controlled

Unit operation

 

 

 

 

by

 

 

 

 

 

 

00

Verification

ON

Unit

Indicates that the data in the slave registered in the scan list is different

 

Error Flag

 

 

from the data from the actual slave. It occurs with the scan list enabled.

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that a verification error has not occurred or turns OFF when a

 

 

 

 

 

verification error is cleared.

 

 

 

 

 

01

Structure

ON

Unit

Indicates that I/O allocations cannot be made with the scan list disabled.

 

Error Flag

 

 

 

 

OFF

Unit

Indicates that a structure error has not occurred or turns OFF when a

 

 

 

 

 

 

 

 

structure error is cleared.

 

 

 

 

 

02

Remote I/O

ON

Unit

Indicates that a remote I/O communications timeout has occurred during

 

Communica-

 

 

remote I/O communications with slaves.

 

tions Error

 

 

Remote I/O communications will stop if DIP switch pin 3 (remote I/O com-

 

Flag

 

 

 

 

 

 

 

munications stop/continue setting for communications errors) on the front

 

 

 

 

 

 

 

 

 

 

panel is ON (stop).

 

 

 

 

 

This error occurs with the scan list enabled or disabled.

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that a remote I/O communications error has not occurred or

 

 

 

 

 

turns OFF when a remote I/O communications error is cleared.

 

 

 

 

 

03

Reserved by

---

---

---

 

system

 

 

 

 

 

 

 

 

04

Invalid Scan

ON

Unit

Indicates that there is incorrect data in the scan list (mismatched check-

 

List Data

 

 

sum). Remote I/O communications in the Unit will stop. (Slave operations

 

Flag

 

 

 

and message communications will continue.)

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that the scan list data is correct.

 

 

 

 

 

Turns OFF when an incorrect scan list data error occurs and then the cor-

 

 

 

 

 

rect scan list is registered.

 

 

 

 

 

05

Remote I/O

ON

Unit

Indicates that the I/O memory in the CPU Unit that is to be refreshed is not

 

Refresh

 

 

present during I/O refreshing for the master. It occurs in several situations,

 

Error Flag

 

 

such as when an I/O area is allocated in an EM bank that is not present.

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that no master I/O refresh errors have occurred.

 

 

 

 

 

06

Reserved by

---

---

---

to

system

 

 

 

07

 

 

 

 

 

 

 

 

 

 

08

Master

ON

Unit

Indicates that an error has occurred in one of the following operations:

 

Function

 

 

• Master enable (word n, bit 06)

 

Enable/

 

 

 

 

 

• Master stop (word n, bit 07)

 

Disable

 

 

 

 

 

Once this bit turns ON, it will remain ON until the operation is successfully

 

Failed Flag

 

 

 

 

 

 

 

completed.

 

 

 

OFF

Unit

Indicates that the error has not occurred. The bit turns OFF when the

 

 

 

 

 

operation is successfully completed.

 

 

 

 

 

 

09

User

 

ON

Unit

Indicates that an error has occurred in one of the following operations:

 

Allocation

 

 

• Master user-set allocations user setting (word n, bit 11)

 

Area Setting

 

 

 

 

 

Once this bit turns ON, it will remain ON until the operation is successfully

 

Failed Flag

 

 

 

 

 

completed.

 

 

 

 

 

 

 

 

 

 

Details on the master user-set allocation results are output to the Master

 

 

 

 

 

User Allocations Setup Table.

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that the error has not occurred. The bit turns OFF when the

 

 

 

 

 

operation is successfully completed.

 

 

 

 

 

 

74

Page 87
Image 87
Omron CJ1W-DRM21, CS1W-DRM21 operation manual Master Status 1 Word n+12, Word n+12 n = CIO 1,500 + 25 x unit number