User-set Allocations

Section 4-4

4. Multiple masters cannot share the same slave.

MasterMaster

Slave

5.Be sure to use user-set allocations and operate the Master Unit with the scan list enabled if multiple masters are connected to a single network. Communications will not be possible if there is more than one master with the scan list disabled connected to a network.

Changing System Components

In the following situations, the table must be reset, the Master User Alloca- tions Switch (word n, bit 11) turned ON, and the scan list recreated:

Adding a slave

Removing a slave

Changing a node address

Changing a node allocation There is no need to clear the scan list.

Example Settings for User-set Allocations through Allocated DM Area Words

This example uses the following settings for unit number 0.

OUT block 1 area and first word: WR (04 Hex), 50 (0032 Hex)

IN block 1 area and first word: WR (04 Hex), 100 (0064 Hex)

Allocation Size Setup Table area and first word: DM (03 Hex), 00100 (0064 Hex)

This example shows user-set allocations for the following slaves.

Node address

 

Outputs

Inputs

 

Product

0

 

16 pts

0 pts

 

16-pt Transistor Output Terminal (DRT1-

 

 

 

 

 

OD16)

 

 

 

 

 

 

1

 

8 pts

8 pts

 

8-pt input and 8-pt Output Environment-

 

 

 

 

 

resistant Terminal (DRT1-MD16C)

 

 

 

 

 

 

2

 

16 pts

16 pts

 

CQM I/O Link Terminal (CQM1-DRT21)

 

 

 

 

 

 

3

 

0 pts

8 pts

 

8-pt Transistor Input Terminal (DRT1-

 

 

 

 

 

ID08)

 

 

 

 

 

 

4

 

None

 

 

---

 

 

 

 

 

 

5

 

160 pts

160 pts

 

CS/CJ-series DeviceNet Unit (CS1W-

 

 

 

 

 

DRM21) (Slave Unit)

 

 

 

 

 

 

 

Master User Allocations Table

 

 

 

OUT block 1 area: WR (04 Hex)

 

 

 

First word of OUT block 1: 50 (0032 Hex)

 

 

IN block 1 area: WR (04 Hex)

 

 

 

First word of IN block 1: 100 (0064 Hex)

 

 

Area for the Allocation Size Setup Table: DM (03 Hex)

 

 

First word of the Allocation Size Setup Table: 00100 (0064 Hex)