Omron CJ1W-DRM21, CS1W-DRM21 File Names, Saving Files from Configurator to Memory Card

Models: CJ1W-DRM21 CS1W-DRM21

1 274
Download 274 pages 23.02 Kb
Page 257
Image 257

Memory Card Backup Functions

Appendix D

3. Saving Files from Configurator to Memory Card

Device parameter files (.dvf files) for this DeviceNet Unit that have been created using the Configurator can be saved on the Memory Card via the HMC-AP001 Memory Card Adaptor as file name DNnnBKUP.dvf (where nn is the Unit number in 2-digit hexadecimal). This DeviceNet Unit can be mounted to the CPU Unit and, by turn- ing ON the Unit Setup File Restore Switch (word n, bit 14), the setup data can be restored to the DeviceNet Unit.

Note The file name when saving setup data to the Memory Card must be DNnnBKUP.dvf (where nn is the Unit number in 2-digit hexadecimal). For example, for unit number 00, the file name must be DN00BKUP.dvf. If the file is saved under another name, the data cannot be restored from the Memory Card to the DeviceNet Unit.

DeviceNet Unit

CPU Unit

 

Configurator (com-

 

 

 

All

Unit Setup File Restore Switch

puter)

 

HMC-AP001 Memory Card Adaptor

 

setup

 

 

Memory Card

 

data

Memory Card

 

Restore

Saving device parameter file

Saved as file name DNnnBKUP.dvf, where nn is the Unit number in 2-digit hexadecimal.)

File Names

The following files are created on the Memory Card.

Directory (fixed): Route and directory.

File name (fixed): DNnnBKUP.dvf (nn: Unit number in 2-digit hexadecimal).

Note The data in the above files is compatible with the data in the DeviceNet Unit device parameter file.

249

Page 257
Image 257
Omron CJ1W-DRM21, CS1W-DRM21 operation manual File Names, Saving Files from Configurator to Memory Card