User-set Allocations

Section 5-3

Areas and Word Ranges for the OUT 1/IN 1 Areas

 

Code

Name

Word range

 

 

 

 

00

Hex

---

The block is not used.

 

 

 

 

01

Hex

CIO Area (CIO)

0000 to 17FF Hex (0 to 6143)

 

 

 

 

03

Hex

DM Area (DM)

0000 to 7FFF Hex (0 to 32767)

 

 

 

 

04

Hex

Word Area (WR)

000 to 01FF Hex (0 to 511)

 

 

 

 

05

Hex

Holding Area (HR)

000 to 01FF Hex (0 to 511)

 

 

 

 

08

Hex to

Expansion Data Memory (EM)

0000 to 7FFF Hex (0 to 32767) for all

14

Hex

Bank 0 to C (13 banks)

banks

 

 

 

 

Step 3: Turn ON the Slave User Allocations Switch

Turn ON the Slave User Allocations Switch (word n+1, bit 11).

Step 4: Turn ON the Slave Enable Switch

Turn ON the Slave Enable Switch (word n+1, bit 06). This will allocated the above areas as slave areas and the DeviceNet Unit will start slave remote I/O communications.

Note Once slave communications are enabled by turning ON the Slave Enable Switch, the Unit will continue to perform slave communications even after the power is turned OFF and back ON again.

Slave User Allocations Table in the Allocated DM Area Words

 

 

 

 

 

Slave output (OUT) area

Master

Bit

 

 

Bit

 

OUT 1

Specify the first word.

 

 

 

 

 

Word m+8

First word

 

 

area

 

 

 

Word m+9

First word of the OUT 1 area

 

specified

 

 

 

 

 

 

Word m+10

OUT 1

Specify the size.

 

 

OUT area

Word m+11

area size

 

to

to

IN block 1

 

 

 

area

Specify the

 

 

 

Word m+12

First word of the IN 1 area

 

 

 

Word m+13

IN 1 area size

first word.

 

 

 

 

 

 

 

 

 

 

Slave input (IN) area

Master

 

 

 

Bit

 

 

Specify the size.

 

 

 

First word

 

 

 

 

 

specified

 

 

 

 

 

to

to

IN area

 

 

 

 

Specify the first word.

Specify the size.

Example Settings for User-set Allocations through Allocated DM Area Words

This example uses the following settings for unit number 0.

OUT block 1 area and first word: WR (04 Hex), 50 (0032 Hex), 20-byte size (14 Hex, 10 words)

IN block 1 area and first word: WR (04 Hex), 100 (0064 Hex), 10-byte size (0A Hex, 5 words)

128