Allocated CIO Area WordsSection 3-2

3-2-10 Slave Status 2 (Word n+15)

Word

Bit 15

Bit 08 Bit 07

Bit 00

n+15

Slave I/O Allocation Status

 

 

Master Node Address

 

 

 

 

 

Master Node Addresses

This indicates the node address of the remote master for slave communica-

 

tions.

 

 

 

 

 

 

 

Name

Range

Details

 

 

 

 

 

Master Node

0000 to 003F Hex

This information is valid when the Remote

 

Address

(0 to 63)

I/O Communications Flag (word n+14, bit

 

 

 

14 or 15) is ON in Slave Status 1.

 

 

 

 

Slave I/O Allocation Status This indicates the I/O allocation status of the slave.

Code

Details

 

 

00 Hex

Unit starting up

 

 

01 Hex

Fixed Allocation Setting 1

 

 

02 Hex

Fixed Allocation Setting 2

 

 

03 Hex

Fixed Allocation Setting 3

 

 

20 Hex

User-set allocations using allocated DM Area words

 

 

30 Hex

Set from the Configurator

 

 

80 Hex

Slave function disabled

 

 

3-2-11 Registered Slave Table (Words n+16 to n+19)

This table indicates the slaves that are registered in the master scan list. The bits correspond to node addresses. This table is updated when the Unit starts up and when a scan list is registered.

 

Bit15

Bit14

Bit13

Bit12

Bit11

Bit10

Bit09

Bit08 Bit07

Bit06

Bit05

Bit04

Bit03

Bit02

Bit01

Bit00

n+16

15

14

13

12

11

 

10

09

 

08

07

06

05

04

03

 

02

01

 

00

n+17

31

30

29

28

27

 

26

25

 

24

23

22

21

20

19

 

18

17

 

16

n+18

47

46

45

44

43

 

42

41

 

40

39

38

37

36

35

 

34

33

 

32

n+19

63

62

61

60

59

 

58

57

 

56

55

54

53

52

51

 

50

49

 

48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation with the Scan This table indicates the slaves to which a connection has been established at

List Disabledleast once. When registering a scan list using the Scan List Enable Switch (word n, bit 00), the bits corresponding to the slaves that are registered are turned ON in this table.

Operation with the Scan

This table indicates the slaves that have been registered in the scan list.

List Enabled

 

 

 

 

 

 

 

 

Bit

Name

Status

Controlled

Unit operation

 

 

 

by

 

 

 

 

 

 

Slave

ON

Unit

With the scan list disabled: Indicates slaves to which a connection has

 

Registered

 

 

been established at least once.

 

Flags

 

 

With the scan list enabled: Indicates that a slave has been registered in

 

 

 

 

 

 

 

 

the scan list.

 

 

 

 

 

 

 

OFF

Unit

Indicates that a slave has not been registered in the scan list.

 

 

 

 

 

78

Page 91
Image 91