Omron CJ1W-DRM21, CS1W-DRM21 operation manual Slave Unit Func Oper Tion Ating Mode

Models: CJ1W-DRM21 CS1W-DRM21

1 274
Download 274 pages 23.02 Kb
Page 79
Image 79

Allocated CIO Area Words

 

 

Section 3-2

 

 

 

 

 

 

 

 

 

Bit

Name

Status

Con-

Unit operation

Operation

Default

 

 

 

trolled by

 

conditions

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU

Slave

 

 

 

 

 

 

 

Unit

func-

 

 

 

 

 

 

 

oper-

tion

 

 

 

 

 

 

 

ating

 

 

 

 

 

 

 

 

mode

 

 

 

06

Slave

OFF

User

Enables slave communications. (The Unit automatically

Pro-

Dis-

Slave

 

Enable

ON

 

restarts.)

gram

abled

disabled

 

Switch

 

 

To use fixed allocations, turn this switch ON after turning

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON a Slave Fixed Allocation Setting Switch (word n+1,

 

 

 

 

 

 

 

 

bits 08 to 10). To used user-set allocations, turn this

 

 

 

 

 

 

 

 

switch ON after turning ON the User Setting Switch

 

 

 

 

 

 

 

 

(word n+1, bit 11).

 

 

 

 

 

 

 

 

Once enabled, the Unit will function as a slave regard-

 

 

 

 

 

 

 

 

less of whether the power is turned OFF and back ON

 

 

 

 

 

 

 

 

again until the Slave Stop Switch (word n+1, bit 07) is

 

 

 

 

 

 

 

 

turned ON.

 

 

 

 

 

 

 

 

Note 1. Slave communications are enabled in the

 

 

 

 

 

 

 

 

default setting.

 

 

 

 

 

 

 

 

2. If this bit is turned ON with Slave enabled, a

 

 

 

 

 

 

 

 

Unit status error will occur and a C2 error will

 

 

 

 

 

 

 

 

be displayed on the 7-segment display. The

 

 

 

 

 

 

 

 

7-segment display will go out automatically

 

 

 

 

 

 

 

 

after 30 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Unit

Returns to OFF at the start of slave communications.

 

 

 

 

 

 

 

 

 

 

 

 

07

Slave Stop

OFF

User

Stops slave communications. (The Unit automatically

Pro-

Dis-

Slave

 

Switch

ON

 

restarts.) Turn this switch ON if the Unit will be used only

gram

abled

disabled

 

 

 

 

for master communications.

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Unit

Returns to OFF after slave communications stop.

 

 

 

 

 

 

 

 

 

 

 

 

 

66

Page 79
Image 79
Omron CJ1W-DRM21, CS1W-DRM21 operation manual Slave Unit Func Oper Tion Ating Mode