Allocated CIO Area Words

 

 

Section 3-2

 

 

 

 

 

 

 

 

 

 

Bit

Name

Status

Con-

Unit operation

Operation condi-

Default

 

 

 

trolled

 

 

tions

 

setting

 

 

 

by

 

 

 

 

 

 

 

 

 

 

CPU

Mas-

Scan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

ter

list

 

 

 

 

 

 

 

oper-

func-

sta-

 

 

 

 

 

 

 

ating

tion

tus

 

 

 

 

 

 

 

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

02

Remote I/

OFF

User

Starts remote I/O communications.

---

En-

---

None

 

O Com-

ON

 

Note 1. The switch is ignored if remote I/O commu-

 

abled

 

 

 

 

munica-

 

 

 

 

 

 

 

 

 

 

nications are already running.

 

 

 

 

 

 

tions Start

 

 

 

 

 

 

 

 

 

 

2. This switch is used to restart remote I/O

 

 

 

 

 

 

Switch

 

 

 

 

 

 

 

 

 

 

communications if they are stopped by a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

communications error.

 

 

 

 

 

 

 

 

 

3. Communications with a slave will fail even if

 

 

 

 

 

 

 

 

 

remote I/O communications are started if

 

 

 

 

 

 

 

 

 

the Disconnect/Connect Switch (corre-

 

 

 

 

 

 

 

 

 

sponding bit in words n+6 to 9) is ON (1:

 

 

 

 

 

 

 

 

 

Connect).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Unit

Returns to OFF at the start of remote I/O communica-

 

 

 

 

 

 

 

 

 

tions.

 

 

 

 

 

 

 

 

 

Note This switch will stop remote I/O communications

 

 

 

 

 

 

 

 

 

if DIP switch pin 3 on the front panel (remote I/O

 

 

 

 

 

 

 

 

 

communications start/stop with a communica-

 

 

 

 

 

 

 

 

 

tions error) is ON (stop) and there is an ongoing

 

 

 

 

 

 

 

 

 

communications or send error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

Remote I/O

OFF

User

This switch functions the same as bit 02 above.

---

En-

---

 

 

 

Communi-

ON

 

Note This switch is used to ensure compatibility

 

abled

 

 

 

 

cations

 

 

 

 

 

 

 

 

Start

OFF

Unit

between the software switches and C200H

 

 

 

 

 

 

Switch

 

 

DeviceNet Master (C200HW-DRM21-V1).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

Remote I/

OFF

User

Stops remote I/O communications.

---

En-

---

 

 

 

O Com-

ON

 

Once remote I/O communications have been stopped,

 

abled

 

 

 

 

munica-

 

 

 

 

 

 

 

 

 

 

they will remain stopped until the Unit has been

 

 

 

 

 

 

tions Stop

 

 

 

 

 

 

 

 

 

 

restarted or the remote I/O communications have been

 

 

 

 

 

 

Switch

 

 

 

 

 

 

 

 

 

 

restarted (i.e., until the Remote I/O Communications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start Switch is turned ON).

 

 

 

 

 

 

 

 

 

Note 1. The switch is ignored if remote I/O commu-

 

 

 

 

 

 

 

 

 

nications are already stopped.

 

 

 

 

 

 

 

 

 

2. Message communications will remain

 

 

 

 

 

 

 

 

 

enabled even if remote I/O communications

 

 

 

 

 

 

 

 

 

have stopped.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Unit

Returns to OFF when remote I/O communications

 

 

 

 

 

 

 

 

 

stop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05

Reserved

---

---

---

---

---

---

---

 

 

by system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

Page 75
Image 75