Nomenclature and Functions

Section 2-1

2. Two-digit, 7-segment display

MS

1. Status indicators

NS

3. Dot indicators

2-1-2 Status Indicators: MS and NS

The MS (Module Status) indicator indicates the status of the node itself and the NS (Network Status) indicator indicates the status of the network.

The MS and NS indicators can be green or red and they can be OFF, ON, or flashing (alternating 0.5-s ON and 0.5-s OFF.) The following table shows the meaning of these indicator conditions.

Indi-

Color

Status

Meaning (likely errors)

cator

 

 

 

 

 

 

 

MS

Green

ON

Normal operating status

 

 

 

Communications are being performed normally.

 

 

 

 

 

Red

ON

A non-recoverable, fatal error has occurred.

 

 

 

(Watchdog timer error, memory error, or system error.)

 

 

 

Replace the DeviceNet Unit.

 

 

 

 

 

 

Flashing

A recoverable, non-fatal error has occurred. (Structure

 

 

 

error, switch setting error, PC initialization error, PC inter-

 

 

 

face error, or routing table error.)

 

 

 

Correct the error and reset the Unit.

 

 

 

 

 

---

OFF

Power isn’t being supplied or the Unit is being reset.

 

 

 

 

NS

Green

ON

The Unit is online with the network and remote I/O com-

 

 

 

munications have been established with a slave regis-

 

 

 

tered in the scan list or message communications have

 

 

 

been established.

 

 

 

 

 

 

Flashing

The Unit is online with the network, but neither remote I/

 

 

 

O communications nor message communications have

 

 

 

been established. Either the scan list is being read, or

 

 

 

both remote I/O communications and message commu-

 

 

 

nications are disabled.

 

 

 

 

 

Red

ON

A fatal communications error has occurred. Network

 

 

 

communications are not possible.

 

 

 

(Node address duplicated or Bus Off error)

 

 

 

 

 

 

Flashing

A non-fatal communications error has occurred. (Com-

 

 

 

munications error, setup error, or verification error)

 

 

 

 

 

---

OFF

The Unit is not online with the network.

 

 

 

(There is no network power supply, the Unit is being

 

 

 

reset, a minor failure, or a sending error has occurred.)

 

 

 

 

47

Page 61
Image 61