Allocated CIO Area Words

 

Section 3-2

 

 

 

 

 

 

Bit

Name

Status

 

Controlled

Unit operation

 

 

 

 

by

 

 

 

 

 

 

 

01

Remote I/O

ON

 

Unit

Indicates that remote I/O communications are being performed for the

 

Communica-

 

 

 

master function. Normally, the Unit will perform remote I/O communica-

 

tions Flag

 

 

 

tions automatically.

 

 

 

 

 

Note This bit only indicates the start of remote I/O communications, and

 

 

 

 

 

does not indicate whether data has actually been exchanged with

 

 

 

 

 

slaves. Actual data exchange between one or more slaves is mon-

 

 

 

 

 

itored from I/O Data Communications Flag (word n+12 bit 15).

 

 

 

 

 

Therefore use I/O Data Communications Flag rather than this bit

 

 

 

 

 

as the input condition in I/O processing for slaves from the ladder

 

 

 

 

 

program.

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates remote I/O communications have stopped. This bit turns OFF in

 

 

 

 

 

order to stop communications under the following conditions:

 

 

 

 

 

• No slaves are registered in the scan list.

 

 

 

 

 

• Invalid Setup Data Flag (word n+12, bit 04)

 

 

 

 

 

• A remote I/O communications error or sending error (network power er-

 

 

 

 

 

ror or send timeout error) occurred with DIP switch pin 3 (remote I/O

 

 

 

 

 

communications stop/continue setting for communications errors) on

 

 

 

 

 

the front panel turned ON.

 

 

 

 

 

• The remote I/O Communications Stop Switch (word n, bit 04) is ON.

 

 

 

 

 

 

02

Reserved by

---

 

---

---

 

system

 

 

 

 

 

 

 

 

 

 

03

Master

ON

 

Unit

Indicates that master communications are enabled (Unit is operating as a

 

Function

 

 

 

Master) (default setting).

 

Enabled

 

 

 

 

 

OFF

 

Unit

Indicates that master communications are disabled.

 

Flag

 

 

 

 

 

 

 

 

 

 

 

 

04

Scan List

ON

 

Unit

Indicates that the Unit is operating with the scan list disabled (default set-

 

Disabled

 

 

 

ting).

 

Flag

 

 

 

 

 

OFF

 

Unit

Indicates that the Unit is operating with the scan list enabled.

 

 

 

 

 

 

 

 

 

05

Reserved by

---

 

---

---

 

system

 

 

 

 

 

 

 

 

 

 

06

Automatic

ON

 

Unit

Indicates that the connection type was automatically set in the slave scan

 

Slave

 

 

 

list.

 

Connection

 

 

 

This flag is valid only with slave communications enabled.

 

Flag

 

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates that the connection type was set from the Configurator in the

 

 

 

 

 

 

 

 

slave scan list.

 

 

 

 

 

Note The type of connection in slave communications cannot be speci-

 

 

 

 

 

fied without the Configurator. If it is not set from the Configurator, it

 

 

 

 

 

will be set automatically.

 

 

 

 

 

 

07

Slave Func-

ON

 

Unit

Indicates that slave communications are enabled.

 

tion Enabled

 

 

 

 

 

OFF

 

Unit

Indicates that slave communications are disabled (default setting).

 

Flag

 

 

 

 

 

 

 

 

 

 

 

 

08

File Read/

ON

 

Unit

Indicates that an error has occurred when user setup data is read from a

 

Write Error

 

 

 

Memory Card in the CPU Unit or when data is written as a file to a Mem-

 

Flag

 

 

 

ory Card.

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates that the error has not occurred. Turns OFF when the Unit has

 

 

 

 

 

successfully completed the operation.

 

 

 

 

 

 

09

Reserved by

---

 

---

---

to

system

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

15

Error His-

ON

 

Unit

Indicates that an error history has been registered. Turns ON at the first

 

tory Flag

 

 

 

error history for the Unit.

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates that no errors have been registered in the error history. Turns

 

 

 

 

 

OFF when the Unit receives an error history clear request.

 

 

 

 

 

 

73

Page 86
Image 86