List of Usage Methods by PurposeSection 1-7

1-7

List of Usage Methods by Purpose

 

 

 

 

 

 

 

 

 

Situation

 

Action

Page

 

 

 

 

 

 

Design

 

Allocating any

In order of node

Set using the allocated DM Area words.

108

 

 

words for

addresses

(Master User Allocations Setup Table and Alloca-

 

 

 

remote I/O

 

tion Size Setup Table)

 

 

 

 

 

Note Allocations using allocated DM Area words:

 

 

 

 

 

Order of node addresses and two blocks,

 

 

 

 

 

OUT 1 and IN 1.

 

 

 

 

 

 

 

 

 

 

Not in order of

Set using the configurator.

113

 

 

 

node

Note Allocations using Configurator: Any node

 

 

 

 

addresses

 

 

 

 

address order and four blocks, OUT 1, IN 1,

 

 

 

 

 

 

 

 

 

 

OUT 2 and IN 2. Allocation is much easier

 

 

 

 

 

using a wizard.

 

 

 

 

 

 

 

 

 

Using the Unit as a slave

Set using the allocated DM Area words.

122

 

 

 

 

 

 

 

Performing message communi-

Execute communications instructions from the user

134

 

 

cations between PCs to which

program.

 

 

 

DeviceNet Units are mounted

 

 

 

 

 

 

 

 

 

Mounting multiple DeviceNet

3 Units max. with fixed allocations

92

 

 

Units using master communica-

16 Units max. with user-set allocations

 

 

 

tions to a single PC

 

 

 

 

 

 

 

 

 

Mounting multiple DeviceNet

3 Units max. with fixed allocations

122

 

 

Units using slave communica-

16 Units max. with user-set allocations

 

 

 

tions to a single PC

 

 

 

 

 

 

 

 

 

Connecting multiple PCs (master

Supported by user-set allocations using allocated

122

 

 

communications) in a network

DM Area words or user-set allocations using the

 

 

 

 

 

Configurator.

 

 

 

 

 

 

 

 

Connecting a single Master PC

Set multiple PCs to Slave mode from the allocated

122

 

 

and multiple Slave PCs in a net-

DM Area words or the Configurator.

 

 

 

work

 

Note Up to 64 Units may be on a network.

 

 

 

 

 

 

 

 

 

 

(Example: 1 Master PC and 63 Slave PCs)

 

 

 

 

 

 

 

 

Sending DeviceNet explicit mes-

Set the FINS command code to 2801.

138

 

 

sages

 

 

 

 

 

 

 

 

 

 

Setting the node address for a

Set the rotary switches on the front of the

49

 

 

DeviceNet Unit

 

DeviceNet Unit.

 

 

 

 

 

 

 

 

Setting the baud rate for the

Set the DIP switch on the front of the DeviceNet

50

 

 

DeviceNet Unit

 

Unit.

 

 

 

 

 

 

 

 

Stopping remote I/O communica-

Set the DIP switch on the front of the DeviceNet

51

 

 

tions for communications errors

Unit.

 

 

 

 

 

 

 

 

Holding OUT data in slave I/O

Set the DIP switch on the front of the DeviceNet

51

 

 

memory for communications

Unit.

 

 

 

errors

 

 

 

 

 

 

 

 

 