Allocated CIO Area Words

 

 

Section 3-2

 

 

 

 

 

 

Bit

Name

Status

Controlled

C200HW-

Details and CS1W-DRM21 status

 

 

 

by

DRM21-V1

 

 

 

 

 

status

 

 

 

 

 

 

 

03

Configura-

ON/OFF

Unit

Configura-

This bit turns ON if any of the following flags turn ON:

 

tion Error

 

 

tion Error

• Routing Table Error Flag (word n+10, bit 12)

 

Flag

 

 

Flag

 

 

 

• Invalid Message Timer List Flag (word n+10, bit 13)

 

 

 

 

 

 

 

 

 

 

• Invalid Scan List Data Flag (word n+12, bit 04)

 

 

 

 

 

• Remote I/O Refresh Error Flag (word n+12, bit 05)

 

 

 

 

 

Note The C200HW-DRM21-V1 does not support slave

 

 

 

 

 

communications. Scan list data errors for slave

 

 

 

 

 

communications are not relevant.

 

 

 

 

 

 

04

Structure

ON/OFF

Unit

Structure

This is the same as the Structure Error Flag in word n+12,

 

Error Flag

 

 

Error Flag

bit 01.

 

 

 

 

 

 

05

Send Error

ON/OFF

Unit

Send Error

This bit turns ON if any one of the following bits turns ON:

 

Flag

 

 

Flag

• Network Power Error Flag (word n+10, bit 07)

 

 

 

 

 

 

 

 

 

 

• Send Timeout Flag (word n+10, bit 08)

 

 

 

 

 

 

06

Communica-

ON/OFF

Unit

Communica-

This is the same as the Remote I/O Communications

 

tions Error

 

 

tions Error

Flag (word n+12, bit 02).

 

Flag

 

 

Flag

 

 

 

 

 

 

 

07

Verification

ON/OFF

Unit

Verification

This is the same as the Verification Error Flag in word

 

Error Flag

 

 

Error Flag

n+12, bit 00.

 

 

 

 

 

 

08

I/O Data

ON/OFF

Unit

I/O Data

This operates in the reverse way of the Remote I/O Com-

 

Communica-

 

 

Communica-

munications Flag (word n+11 bit 01).

 

tions Not

 

 

tions Not

 

 

Running Flag

 

 

Running

 

 

 

 

 

Flag

 

 

 

 

 

 

 

09

Reserved by

---

---

Scan List

---

 

system

 

 

Operation

 

 

 

 

 

Completed

 

 

 

 

 

Flag

 

 

 

 

 

 

 

10

Reserved by

---

---

Scan List

---

 

system

 

 

Operation

 

 

 

 

 

Error Flag

 

 

 

 

 

 

 

11

Reserved by

---

---

Communica-

---

 

system

 

 

tions Error

 

 

 

 

 

Stop Cleared

 

 

 

 

 

Flag

 

 

 

 

 

 

 

12

Message

ON/OFF

Unit

Message

The same as the Online Flag in word n+11, bit 00.

 

Communica-

 

 

Communica-

Note When executing message communications

 

tions Permit-

 

 

tions Permit-

 

 

 

instructions (SEND/RECV/CMND) from the ladder

 

ted Flag

 

 

ted Flag

 

 

 

program, use an AND of input conditions for the

 

 

 

 

 

 

 

 

 

 

Network Communications Enabled Flag in the

 

 

 

 

 

CPU Unit (A20200 to A20207) and this bit.

 

 

 

 

 

 

13

Invalid Scan

ON/OFF

Unit

Invalid Scan

The same operation as the Invalid Scan List Data Flag

 

List Data Flag

 

 

List Data Flag

(word n+11, bit 04).

 

 

 

 

 

 

14

Error Flag

ON/OFF

Unit

Error Flag

This bit turns ON if bit 00, 01 or 03 to 07 in this word

 

 

 

 

 

(n+24) turns ON.

 

 

 

 

 

 

15

Remote I/O

ON/OFF

Unit

Remote I/O

The same as I/O Data Communications Flag (word n+12

 

Communica-

 

 

Communica-

bit 15).

 

tions Flag

 

 

tions Flag

 

Note Although the bit configurations are the same, the word addresses are different (because this is a CS/CJ-series CPU Bus Unit). Change the words using a replacement operation from the Programming Device.

80