Sending Explicit Messages

Section 6-4

D:First response word

C:First control data word

Command data is set in order starting with the word specified for the CMND(490) operand S (first command word) and continuing with words with higher addresses in I/O memory in the command block format.

Command Format Example: Writing Error Clear Codes to the CPU Unit

Set in this order starting from the word specified for the CMND(490) operand S (first command word) and continuing with words with higher addresses.

28 01 01 10 00 2F 00 00 65 FE FF

 

 

 

 

 

 

 

Command

Service

Instance ID

 

code

Code

 

Service Data

 

Destination

Class ID

node address

 

Method for Setting Data from CMND(490) Operand S

Bit

FINS command code

Node address, Service Code

Class ID

Instance ID

Service Data

Service Data

In the same way, response data is set from the starting with the word specified for CMND(490) operand D (first response word) and continuing with words with higher addresses in I/O memory in the response block format.

Note Service data that is in word (2-byte) or double-word (4-byte) units, such as word data and ERROR CLEAR codes, is specified from low to high (U) bytes in command block format. For example, to specify word data $1234, specify $34 and then $12. To specify $12345678, specify $78 to $56 to $34 to $12. The command blocks are shown in the following diagram.