Omron CS1W-DRM21 Master Status 2 Word n+13, Master I/O Allocation Status, Code Details

Models: CJ1W-DRM21 CS1W-DRM21

1 274
Download 274 pages 23.02 Kb
Page 88
Image 88

Allocated CIO Area Words

 

Section 3-2

 

 

 

 

 

 

Bit

Name

Status

 

Controlled

Unit operation

 

 

 

 

by

 

 

 

 

 

 

 

10

Fixed

ON

 

Unit

Indicates that an error has occurred in one of the following operations:

 

Allocation

 

 

 

• Fixed Allocation Setting 1 (word n, bit 08)

 

Area Setting

 

 

 

 

 

 

 

• Fixed Allocation Setting 2 (word n, bit 09)

 

Failed Flag

 

 

 

 

 

 

 

• Fixed Allocation Setting 3 (word n, bit 10)

 

 

 

 

 

 

 

 

 

 

Once this bit turns ON, it will remain ON until the operation is successfully

 

 

 

 

 

completed.

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates that the error has not occurred. The bit turns OFF when the

 

 

 

 

 

operation is successfully completed.

 

 

 

 

 

 

11

Scan List

ON

 

Unit

Indicates that an error has occurred in one of the following operations:

 

Register/

 

 

 

• Scan list enabled (word n, bit 00)

 

Clear Failed

 

 

 

 

 

 

 

• Scan list clear (word n, bit 01)

 

Flag

 

 

 

 

 

 

 

Once this bit turns ON, it will remain ON until the operation is successfully

 

 

 

 

 

 

 

 

 

 

completed.

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates that the error has not occurred. The bit turns OFF when the

 

 

 

 

 

operation is successfully completed.

 

 

 

 

 

 

12

Communica-

ON

 

Unit

Indicates that an error has occurred when setting the communications

 

tions Cycle

 

 

 

cycle time (word n, bit 12).

 

Time

 

 

 

Once this bit turns ON, it will remain ON until the next communications

 

Setting

 

 

 

 

 

 

 

cycle time is set.

 

Failed Flag

 

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates that the error has not occurred. The bit turns OFF when the

 

 

 

 

 

 

 

 

operation is successfully completed.

 

 

 

 

 

 

13

Reserved by

---

 

---

---

to

system

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

15

I/O Data

ON

 

Unit

Indicates that at least one slave is performing remote I/O communications.

 

Communica-

 

 

 

Usage example: When writing the ladder program for remote I/O commu-

 

tions Flag

 

 

 

 

 

 

 

nications, set a NO input condition for this bit to control slave I/O process-

 

 

 

 

 

 

 

 

 

 

ing.

 

 

 

 

 

 

 

 

OFF

 

Unit

Indicates that remote I/O communications are not being conducted with

 

 

 

 

 

any slaves.

 

 

 

 

 

 

3-2-8 Master Status 2 (Word n+13)

The leftmost eight bits indicate the status of master I/O allocations.

Word

Bit 15

Bit 08 Bit 07

Bit 00

n+13

Master I/O Allocation Status

 

 

Reserved by system

 

 

 

 

 

Master I/O Allocation Status

Code

Details

 

 

00 Hex

Unit starting up

 

 

01 Hex

Fixed allocation status 1 (with the scan list disabled)

 

 

02 Hex

Fixed allocation status 2 (with the scan list disabled)

 

 

03 Hex

Fixed allocation status 3 (with the scan list disabled)

 

 

11 Hex

Fixed allocation status 1

 

 

12 Hex

Fixed allocation status 2

 

 

13 Hex

Fixed allocation status 3

 

 

20 Hex

User-set allocations in the allocated DM Area words

 

 

30 Hex

User-set allocations from the Configurator

 

 

80 Hex

Master function disabled

 

 

75

Page 88
Image 88
Omron CS1W-DRM21, CJ1W-DRM21 operation manual Master Status 2 Word n+13, Master I/O Allocation Status, Code Details