Allocated DM Area Words

 

Section 3-3

 

 

 

 

 

Bit

Name

Status

Controlled

Unit operation

 

 

 

by

 

 

 

 

 

 

03, 11

Slave

ON

Unit

Indicates that an error has occurred in remote I/O communications

 

Remote I/O

 

 

with the Slave.

 

Communica-

 

 

This bit turns ON if a timeout occurs in at least one connection with

 

tions Error

 

 

 

 

 

multiple connections set.

 

Flag

 

 

 

 

 

This error occurs with the scan list enabled or disabled.

 

 

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that a remote I/O communications error has not occurred

 

 

 

 

or turns OFF when a remote I/O communications error is cleared.

 

 

 

 

 

04, 12

Reserved by

---

---

---

 

system

 

 

 

 

 

 

 

 

05, 13

Master COS

ON

Unit

Indicates that COS sent to a slave destination failed.

 

Send Fail-

 

 

Use the Master COS Send Switch (n+2/n+3/n+4/n+5 words) to send

 

ure Flag

 

 

 

 

 

COS.

 

 

 

 

 

 

 

 

The following may be cause failure of COS signal transmission.

 

 

 

 

• Remote I/O communications stopped

 

 

 

 

• A COS connection was not established

 

 

 

 

• Bus OFF has occurred.

 

 

 

 

• A network power error has occurred.

 

 

 

 

• A send timeout has occurred.

 

 

 

 

Once this bit turns ON, it will remain ON until the operation is suc-

 

 

 

 

cessfully completed.

 

 

 

 

 

 

 

OFF

Unit

Indicates that the error has not occurred. The bit turns OFF when

 

 

 

 

COS is successfully sent.

 

 

 

 

 

06, 14

Scan List

ON

Unit

Indicates that the slave is registered in the scan list.

 

Registration

 

 

 

 

OFF

Unit

The Unit is operating with the scan list disabled or the Unit is not reg-

 

Flag

 

 

 

istered in the scan list.

 

 

 

 

 

 

 

 

 

07, 15

Remote I/O

ON

Unit

Indicates that normal remote I/O communications were conducted

 

Communica-

 

 

with the slaves at all set connections.

 

tions Flag

 

 

This bit turns OFF if a timeout occurs in at least one connection with

 

 

 

 

 

 

 

 

multiple connections set.

 

 

 

 

 

 

 

OFF

Unit

Indicates that remote I/O communications failed (no slave present,

 

 

 

 

no scan list registered, verification error, structure error) or that a

 

 

 

 

communications error is occurring.

 

 

 

 

 

90

Page 103
Image 103