Omron CS1W-DRM21 Slave Detailed Status, Figuration Slave with the scan list disabled Error Flags

Models: CJ1W-DRM21 CS1W-DRM21

1 274
Download 274 pages 23.02 Kb
Page 102
Image 102

Allocated DM Area Words

 

 

 

Section 3-3

Note OUT2 is not used.

 

 

 

Ranges

 

 

 

 

 

 

 

 

 

 

 

Name

Range

 

Details

 

 

 

 

 

 

 

OUT 1/2 area

 

See Areas and Word

 

Shows the area.

 

 

 

Ranges.

 

 

 

First word in the OUT block

 

Shows the first word for the

 

 

 

 

1/2

 

 

 

area.

 

 

 

 

 

 

 

OUT 1/2 area size

00 to C8 Hex

 

Shows the area by size in

 

 

 

(0 to 200 bytes)

 

bytes.

 

 

 

 

 

 

 

IN 1/2 area

 

See Areas and Word

 

Shows the area.

 

 

 

Ranges.

 

 

 

First word in the IN

 

Shows the first word for the

 

 

 

 

blocks1/2

 

 

 

area.

 

 

 

 

 

 

 

IN 1/2 area size

00 to C8 Hex

 

Shows the block size in

 

 

 

(0 to 200 bytes)

 

bytes.

 

 

 

 

 

 

Areas and Word Ranges

 

 

 

 

 

 

 

 

 

 

 

Code

 

Name

 

Word range

 

 

 

 

 

 

00 Hex

---

 

The block is not used.

 

 

 

 

 

01 Hex

CIO Area (CIO)

0000 to 17FF Hex (0 to 6143)

 

 

 

 

 

03 Hex

Data Memory (DM)

0000 to 7FFF Hex (0 to 32767)

 

 

 

 

 

04 Hex

Work Area (WR)

0000 to 01FF Hex (0 to 511)

 

 

 

 

 

05 Hex

Holding Relay (HR)

0000 to 01FF Hex (0 to 511)

 

 

 

 

 

08 to 14 Hex

Expansion Data Memory (EM)

0000 to 7FFF Hex (0 to 32767) for

 

 

Bank 0 to bank C (13 banks)

all banks

 

 

 

 

 

 

3-3-8 Slave Detailed Status

The status of the slaves controlled by the master function of the Unit is pro- vided by node address. Each word provides the status of two slaves.

Word

m+37

m+38

to m+68

Bit 15

Bit 08

 

Bit 07

Bit 00

Detailed slave status at node address 1

 

Detailed slave status at node address 0

 

 

 

Detailed slave status at node address 3

 

Detailed slave status at node address 2

 

 

 

 

 

 

 

:

 

 

 

 

Detailed slave status at node address 63

 

Detailed slave status at node address 62

 

 

 

 

 

Bit

Name

Status

Controlled

Unit operation

 

 

 

by

 

 

 

 

 

 

00, 08

Slave Error

ON

Unit

Indicates that a remote I/O communications error has occurred with

 

Flags

 

 

the slave. More specifically, this bit turns ON when at least one of

 

 

 

 

the following errors occurs:

 

 

 

 

• Verification Error Flag (word n+12 bit 00)

 

 

 

 

• Structure Error Flag (word n+12 bit 01)

 

 

 

 

• Remote I/O Communications Error Flag (word n+12 bit 02)

 

 

 

 

 

 

 

OFF

Unit

Indicates that an error has not occurred or turns OFF when the error

 

 

 

 

has been cleared.

 

 

 

 

 

01, 09

Slave Verifi-

ON

Unit

Indicates that the data for the slave registered in the scan list is dif-

 

cation Error

 

 

ferent from the actual Slave. It occurs with the scan list enabled.

 

Flags

 

 

 

 

OFF

Unit

Indicates that a verification error has not occurred or turns OFF

 

 

 

 

 

 

when a verification error is cleared.

 

 

 

 

 

02, 10

Slave Con-

ON

Unit

Indicates that an error that disables I/O allocations has occurred at

 

figuration

 

 

the Slave (with the scan list disabled).

 

Error Flags

 

 

 

 

OFF

Unit

Indicates that a structure error has not occurred or turns OFF when

 

 

 

 

 

 

the structure error is cleared.

 

 

 

 

 

89

Page 102
Image 102
Omron CS1W-DRM21, CJ1W-DRM21 Slave Detailed Status, Figuration Slave with the scan list disabled Error Flags