Allocated CIO Area WordsSection 3-2

3-2-5

Unit Status 1 (Word n+10)

Word n+10 [n = CIO 1,500 + (25 x unit number)]

 

 

 

 

 

Bit

Name

Status

Controlled

Unit operation

 

 

 

 

by

 

 

 

 

 

 

00

Unit Error

ON

Unit

Displays DeviceNet Unit operating errors.

 

Flag

 

 

 

This bit turns ON if any bit from 01 to 15 in Unit Status 1 turns ON. (OR of

 

 

 

 

 

 

 

 

 

 

bits 01 to 15)

 

 

 

 

 

Usage example: When writing the ladder program for remote I/O commu-

 

 

 

 

 

nications, set a NC input conditions for this bit to control Slave I/O pro-

 

 

 

 

 

cessing.

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that the an error has not occurred or turns OFF when the error

 

 

 

 

 

has cleared.

 

 

 

 

 

01

Master

ON

Unit

Indicates that a master error has occurred. (Master Status 1 (See word

 

Function

 

 

n+12.))

 

Error Flag

 

 

The master errors are as follows:

 

 

 

 

 

 

 

 

 

 

• Verification Error Flag (word n+12, bit 00)

 

 

 

 

 

• Structure Error Flag (word n+12, bit 01)

 

 

 

 

 

• Remote I/O Communications Error Flag (word n+12, bit 02)

 

 

 

 

 

• Invalid Scan List Data Flag (word n+12, bit 04)

 

 

 

 

 

• Remote I/O Refresh Error Flag (word n+12, bit 05)

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that the error has not occurred or turns OFF when the error has

 

 

 

 

 

been cleared.

 

 

 

 

 

02

Reserved by

---

---

---

 

system

 

 

 

 

 

 

 

 

03

Slave Func-

ON

Unit

Indicates that a slave error has occurred. (Slave Status 1 (See word

 

tion Error

 

 

n+14.))

 

Flag

 

 

 

The slave errors are as follows:

 

 

 

 

 

 

 

 

 

 

• Remote I/O Communications Error Flag for OUT 1/ IN 1 (word n+14, bit

 

 

 

 

 

02)

 

 

 

 

 

• Remote I/O Communications Error Flag for OUT 2/ IN 2 (word n+14, bit

 

 

 

 

 

03)

 

 

 

 

 

• Invalid Setup Data Flag (word n+14, bit 04)

 

 

 

 

 

• Remote I/O Refresh Error Flag (word n+14, bit 05)

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that the error has not occurred or turns OFF when the error has

 

 

 

 

 

been cleared.

 

 

 

 

 

04

Unit Mem-

ON

Unit

Indicates an error in internal memory where the error history is stored.

 

ory Error

 

 

(The error occurs when the Unit starts up or when the error history is writ-

 

Flag

 

 

 

ten.)

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that the error has not occurred. Once this error has occurred, the

 

 

 

 

 

bit will remain ON and will not return to OFF.

 

 

 

 

 

05

Bus Off Flag

ON

Unit

Indicates that a Bus OFF error (communications were stopped by multiple

 

 

 

 

 

transmissions) has occurred. When a Bus OFF occurs, the Unit goes

 

 

 

 

 

offline and all communications stop (remote I/O communications stop,

 

 

 

 

 

slave operation stop, and message communications are disabled).

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that the error has not occurred. Once this error has occurred, the

 

 

 

 

 

bit will remain ON and will not return to OFF.

 

 

 

 

 

 

06

Node

 

ON

Unit

Indicates a duplicate node address check error when the Unit starts up.

 

Address

 

 

The Unit goes offline and all communications stop. (Remote I/O communi-

 

Duplicated

 

 

cations stop, slave operation stop, and message communications are dis-

 

Flag

 

 

 

abled.)

 

 

 

 

 

 

 

 

 

OFF

Unit

Indicates that the error has not occurred. Once this error has occurred, the

 

 

 

 

 

bit will remain ON and will not return to OFF.

 

 

 

 

 

 

71

Page 84
Image 84
Omron CS1W-DRM21, CJ1W-DRM21 operation manual Unit Status 1 Word n+10, Word n+10 n = CIO 1,500 + 25 x unit number