Allocated DM Area Words

 

Section 3-3

Setting Results

 

 

 

 

 

 

 

Code

Description

Details

 

 

 

 

 

0000

Completed normally

---

 

Hex

 

 

 

 

 

 

 

1101

No area

• Incorrect area setting.

 

Hex

 

• The allocated size in the allocation size setup

 

 

 

table is 0.

 

 

 

 

 

1103

Address range specifi-

The first word is outside the setting range.

 

Hex

cation error

 

 

 

 

 

 

110C

Parameter error

• The OUT or IN size in the allocation size setup

 

Hex

 

table exceeds 200 bytes.

 

 

 

• Both the OUT and IN blocks are set for no allo-

 

 

 

cations.

 

 

 

• No slaves are allocated.

 

 

 

 

 

1104

Address range over-

• The block or the allocation size setup table ex-

 

Hex

flow

ceeds the valid word range.

 

 

 

• The block is larger than 1,000 bytes.

 

 

 

 

 

2201

Wrong operating

The CPU Unit is not in PROGRAM mode.

 

Hex

mode

 

 

 

 

 

 

2201

Unit busy

Service cannot be executed because the Unit is

 

Hex

 

busy.

 

 

 

 

 

2606

Cannot execute ser-

The Unit master communications have not been

 

Hex

vice

disabled.

 

 

 

 

3-3-3 Allocation Size Setup Table

The following allocation size setup tables must be set in the I/O memory in the

CPU Unit to use the Master User Allocations Setup Table.

The number of bytes set in the allocation size setup table are allocated in word units in order of node addresses for OUT block 1 and then IN block 1. Set the sizes within a range from 0 to 200 bytes (100 words).

Word Bit 15

Bit 08 Bit 07

Bit 00

I

 

Node address 0 OUT size (bytes)

 

Node address 0 IN size (bytes)

 

 

 

 

 

I+1

Node address 1 OUT size (bytes)

 

Node address 1 IN size (bytes)

 

 

 

 

 

 

 

:

 

 

 

:

 

I+63

Node address 63 OUT size (bytes)

Node address 63 IN size (bytes)