Omron CS1W-DRM21, CJ1W-DRM21 operation manual DeviceNet Connections, Connection Characteristics

Models: CJ1W-DRM21 CS1W-DRM21

1 274
Download 274 pages 23.02 Kb
Page 244
Image 244

Appendix B

DeviceNet Connections

DeviceNet has several different protocols for remote I/O communications between Master and Slave devices. Connections are units used to monitor those protocols.

There are four kinds of DeviceNet remote I/O communications protocols (connections): Poll, bit–strobe, COS (change of state), and cyclic. CS/CJ-series DeviceNet Units support all four types.

The connection used by the DeviceNet Unit is automatically selected if the Configurator is not used.

If the Configurator is used, the connection can be automatically selected by the DeviceNet Unit or the user can specify the connections for each slave. Up to two connections can be set. COS and cyclic connections cannot be specified at the same time. The characteristics of each connection are outlined in the following table.

Connection

Characteristics

 

 

 

 

Poll

Used for basic I/O.

 

 

 

Bit-strobe

Used for input of 8 bytes or less. Sends broadcasting requests from master and receives input

 

from slaves.

 

 

 

 

COS (Change of

Communications occur at regular cycles (heartbeat timer) and the con-

Note: COS and cyclic

State)

nection is determined by the master or slave sending the data.

connections cannot be

 

Data can be sent only when required, which reduces the network com-

used at the same time.

 

 

 

munications load.

 

 

This connection can be used to send data to the master or slave if the

 

 

master or slave data changes. For DeviceNet Units, the transmission

 

 

timing can be decided in the user program.

 

 

The following points apply for CS/CJ-series DeviceNet Units:

 

 

If the Master COS Send Switch is turned ON, remote I/O communica-

 

 

tions output data can be sent every time from the master using COS to

 

 

the slaves that support COS.

 

 

If the Slave COS Send Switch is turned ON, remote I/O communications

 

 

output data can be sent every time from the slave using COS to the

 

 

master (input data from the perspective of the master).

 

 

Even if the software switch is not turned ON, the COS communications

 

 

using regular cycles (heartbeat timer) can be performed simultaneously.

 

 

Note: This CS/CJ-series DeviceNet Unit is the only OMRON slave that

 

 

supports COS.

 

 

 

 

Cyclic

Communications timing is determined by regular cycles (heartbeat

 

 

timer).

 

 

Masters and slaves send output or input data in regular cycles.

 

 

 

 

Note 1. The C200HW-DRM21-V1 and CVM1-DRM21-V1 DeviceNet Master Units use bit-strobe connections with slaves with 8 or less input points and poll connections with other slaves. The DeviceNet Unit au- tomatically chooses the connection.

2. There can be only one master on each network if COS or cyclic connections are used.

235

Page 244
Image 244
Omron CS1W-DRM21, CJ1W-DRM21 operation manual DeviceNet Connections, Connection Characteristics