FINS Commands and Responses for DeviceNet Units

Appendix C

Response Block

Command End code

Operation Unit

Unit

Master

Master

Slave

Slave

code

status

status 1

status 2

function

function

function

function

 

 

 

 

status 1

status 2

status 1

status 2

End Codes

End code (hex)

Contents

 

 

0000

Normal end

 

 

1001

Command length exceeds maximum command length.

 

 

2606

Service cannot be executed.

 

 

Parameter Details

[Operation status, Units status 1, Unit status 2, Master function status 1, Mas- ter function status 2, Slave function status 1, Slave function status 2] (response)

Operation Status Fixed at 01 hex.

Units status 1, Unit status 2, Master function status 1, Master function sta- tus 2, Slave function status 1, Slave function status 2

The same value as the status in the allocated CIO Area words is returned.

ECHOBACK TEST (0801)

Performs an echo back test (communications test between nodes) between specified nodes.

Command Block

538bytes max.

Command Test data code

Response Block

538 bytes max.

Command End code Test data code

End Codes

End code (hex)

Contents

 

 

0000

Normal end

 

 

1001

Command length exceeds maximum command length.

 

 

1002

The command length is insufficient for the smallest command.

 

There is no test data.

 

 

Parameter Details

[Test Data] (Command, Response)

243

Page 251
Image 251
Omron CJ1W-DRM21, CS1W-DRM21 operation manual Echoback Test, Test Data Command, Response