Nomenclature and Functions

Section 2-1

The following diagram shows the alternating error code/ node address display.

OFF (0.1 s)

OFF (0.3 s)

 

OFF (0.1 s)

OFF (0.3 s)

Error code

 

 

Faulty slave's

Error code

 

 

Faulty slave's

node address

 

 

node address

 

 

(1 s)

 

 

(1 s)

 

 

(1 s)

(1 s)

 

 

 

 

 

 

OFF (0.3 s)

 

OFF (0.1 s)

OFF (0.3 s)

Master's node

 

 

 

Master's

 

 

 

 

error code (1 s)

 

address (1 s)

 

 

 

 

 

 

 

 

 

 

 

 

If there is an error at the DeviceNet Unit.

The master’s error code and master’s node address will be displayed if an error has occurred at the master.

There is no priority in the error codes; all errors that have occurred will be dis- played in order. All error codes begin with letters, so they can be distinguished from node addresses immediately.

Dot Indicators

The following table shows the functions of the dot indicators.

Indicator

Content

Display

 

 

 

Left dot

Scan list enabled/

ON: Master function disabled

 

disabled, master

Flashing: Scan list disabled mode

 

function disabled

 

OFF: Scan list enabled mode

 

 

 

 

 

Right dot

Slave function dis-

ON: Slave function disabled

 

abled

OFF: Slave operating

 

 

 

 

 

2-1-4 Switch Settings

Unit No. Switch

CS1W-DRM21 CJ1W-DRM21

 

 

 

3

56

 

 

10

2

4

 

 

 

8

2

FE

1

 

43

 

D

 

 

7

 

0

 

9

5

C

E

 

A

6

B

 

 

B

 

789A

 

DC

 

Note

Node Address Switches

CS1W-DRM21 CJ1W-DRM21

 

09

 

1

09

 

1

234

 

1

234

 

1

 

 

 

5

 

 

5

 

8

1

8

0

0

 

 

0

 

 

2

7

 

2

7

 

 

 

 

 

 

 

 

 

3

 

3

 

 

87

 

X101

 

87

 

X100

456 X10

 

456 X10

 

 

 

 

 

Use this switch to set the unit number of the DeviceNet Unit as a CPU Bus Unit. The unit number setting determines the CIO and DM area words allo- cated to the Unit as software switches and the status area.

Setting method: One-digit hexadecimal

Setting range: 0 to F

1.The unit number is set to 0 at the factory.

2.Any unit number from 0 to F can be set as long as it hasn’t been set on another CPU Bus Unit connected to the same PC.

3.Use a small flat-blade screwdriver to turn the rotary switches; be careful not to damage the switch.

4.Always turn OFF the PC before changing the unit number setting.

5.If the unit number is the same as one set on another CPU Bus Unit con- nected to the same PC, a duplicate number error will occur in the PC and it won’t be possible to start up the DeviceNet network.

Use these switches to set the node address of the Unit.

Setting method: Two-digit decimal

Setting range: 0 to 63

49

Page 63
Image 63
Omron CJ1W-DRM21, CS1W-DRM21 Switch Settings, Dot Indicators, Following table shows the functions of the dot indicators